background image

Copyright HK Instruments 2021

www.hkinstruments.fi

Installation version 1.0 2021

Pin header

Description

OUT1
OUT2
OUT3
OUT4
GND

Voltage / current output selection

• Current output is an optional

Output 1
Output 2
Output 3
Output 4
Ground

SCHEMATICS

DIMENSIONAL DRAWINGS

INSTALLATION

1) Mount the device in the desired location (see step 1).
2) Route the cables and connect the wires (see step 2).
3) Connect the display cable to the display connector on the PCB. (See 

schematics)

4) The device is now ready for configuration.

 

 WARNING! Apply power only after the device is properly wired.

PM SENSOR

CO₂ SENSOR

VOC SENSOR

A+
B–

24V

GND
GND

OUT1
OUT2
OUT3
OUT4
GND

OUT1

OUT2

OUT3

OUT4

DISPLAY CONNECTOR

2

1

5

4

TEMP OR

rH + TEMP

SENSOR

3

mA-MODULE

Pin header

Description

Open
Connected

Open
Connected

CO

2

 / PM output range selection

400...2000 ppm (CO

2

 models)

0...2000 ppm (CO

2

 models)

0...500 μg/m

3

 (PM models)

0...50 μg/m

3

 (PM models)

Pin header

Description

Open
Connected

Menu lock

Menu lock disabled
Menu lock enabled

1

2

Connector

Description

A+
B-

RS485 Modbus/RTU slave (optional)

DATA+

DATA-

24 V
GND
GND

Power supply

24 VAC/DC ±10 %
Ground
Ground

3

Connector

Description

OUT1
OUT2
OUT3
OUT4
GND

Voltage / current outputs

• Output settings can be modified from the display 

menu

• See the lid label for factory default settings.

Output 1
Output 2
Output 3
Output 4
Ground

4

5

V

m

A

Opening/closing the lid

1) Open the lid by pressing the center from the bottom of the lid as in  

the figure.

2) Close the lid by inserting the top of the lid into the grooves first and 

pushing the bottom edge as in the figure.

Summary of Contents for SIRO Series

Page 1: ...00 ppm 400 2000 ppm selectable via jumper VOC CO eq 400 2000 ppm TVOC ppm 0 30 0 ppm TVOC µg m3 0 10000 µg m3 IAQ index 1 5 UBA rating PM1 PM2 5 PM10 0 50 μg m 0 500 μg m selectable via jumper IAQ index 1 5 WHO rating Temperature 0 50 C Relative humidity 0 100 rH Accuracy CO2 33 ppm 3 of reading typical additional 60 ppm for first weeks VOC 15 of reading typical VOC sensor is tuned for typical IAQ...

Page 2: ...TOR 2 1 5 4 TEMP OR rH TEMP SENSOR 3 mA MODULE Pin header Description Open Connected Open Connected CO2 PM output range selection 400 2000 ppm CO2 models 0 2000 ppm CO2 models 0 500 μg m3 PM models 0 50 μg m3 PM models Pin header Description Open Connected Menu lock Menu lock disabled Menu lock enabled 1 2 Connector Description A B RS485 Modbus RTU slave optional DATA DATA 24 V GND GND Power suppl...

Page 3: ...ill be responsive to changes to the room conditions The Siro should be mounted on a flat surface Do not locate the Siro where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a template and mark the screw holes 3 Mount the wall plate with screws CAUTION Incor...

Page 4: ...ry and stated in the contract The seller will give a new warranty for goods that have been replaced or repaired within the warranty how ever only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or exchange costs Under no circumstance is the seller liable for damages compe...

Reviews: