23
IOM_WPVBZ HE-WPVZ HE_401-1201-4002_208110_200901_EN
PACKAGED COMPACT VERTICAL
– WATER / AIR
WPVBZ HE / WPVZ HE
OPERATION
OPERATION LIMITS
TEMPERATURE
Minimum
Maximum
Cooling cycle
Indoor air inlet Dry bulb
19 ºC
35 ºC
Indoor air inlet Wet bulb
14 ºC
21 ºC
Condensation
35 ºC
65 ºC
Water inlet - Condenser
15 ºC
50 ºC
Heating cycle
Indoor air inlet Wet bulb
18 ºC
24 ºC
Water inlet - Condenser
16 ºC
24 ºC
The units are able to operate at a maximum 1500 m height.