PACKAGED COMPACT VERTICAL
– WATER / AIR
WPVBZ HE / WPVZ HE
HYDRAULIC DIAGRAM
It is compulsory to mount the flow switch
at the water outlet of the unit. The water flow shall be laminar to make sure that
the flow switch works properly: Install the flow switch on a straight section of the tube where there is no section change. The
distance to the switch shall be minimum 6 times the diameter (D) of the tube and at the outlet there shall be a distance of
minimum 3 times the diameter of the tube. Do not install any other component or accessory on that tube. If you use a flow
switch from another supplier (not delivered by Hitecsa), refer to the instructions of the producer and respect the dimensions
as previously stated.
Mesh filter
Flap
3
4
7
8
11
12
Condensate water
drain
Dry tower
Automatic purging
Manometer
Circulation pump
15
Flow switch
1
2
5
6
9
10
Unit
Air duct
Shut-off valve
Water line
Thermometer
13
14
Drain
Buffer tank
WARNING!