ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
TECHNICAL SPECIFICATIONS
MOSAIC HE RANGE
35i
40i
45i
55i
70i
80i
ACVIBA HE
CAPACITIES
Max. cooling capacity (120 Hz)
(1)
kW
35.3
41.0
45.7
56.1
70.7
82.3
Total absorbed power input (120 Hz)
(2)
kW
15.1
20.9
17.7
23.8
30.1
41.7
Min. cooling capacity (20 Hz)
(1)
kW
7.3
9.6
2.4
5.8
7.3
9.6
EER (120 Hz)
-
2.35
1.96
2.59
2.36
2.35
1.98
Seasonal coefficient SEER
(3)
%
4.68
4.13
4.44
4.41
4.65
4.09
Seasonal performance (ηs,
c
)
(3)
-
184.3
162.3
174.6
173.4
183.1
160.5
Max. heating capacity (120 Hz)
(4)
kW
30.3
35.3
41.2
48.8
60.7
70.2
Total absorbed power input (120 Hz)
(2)
kW
10.2
12.9
12.6
16.2
20.4
25.7
COP (120 Hz)
2.97
2.74
3.26
3.01
2.97
2.73
Min. heating capacity (20Hz)
(4)
kW
6.5
7.7
3.7
4.8
6.5
7.7
Seasonal coefficient SCOP
(3)
3.33
3.21
3.38
3.21
3.37
3.23
Seasonal performance (ηs,
h
)
(3)
%
130.1
125.3
132.2
126.2
131.7
126.4
REFRIGERATION CIRCUIT
Refrigerant type
R-410A
Number of circuits
1
2
Power stages
Variable
Global Warming Potential (GWP)
(5)
2088
CIRCUIT 1
Compressor type
Scroll - BLDCM
Number of compressors
1
1
Oil type
PVE - FV50S
Oil volume
L
2.3
1.7
2.3
CIRCUIT 2
Compressor type
-
Scroll - BLDCM
Number of compressors
-
1
Oil type
-
PVE - FV50S
Oil volume
L
-
1.7
2.3
ELECTRICAL SPECIFICATIONS
Power supply
V / ~ / Hz
400 / 3+N /50
Max. operation current
A
33
49
55
68
66
99
(1).
Calculated according to the UNE-EN-14511 standard, for indoor temperature conditions of 27ºC B.S. / 19ºC B.H. and 35ºC
outdoor temperature. Frequency of the compressor as stated above.
(2).
Nominal consumption of the entire equipment (compressors and fans) in nominal conditions, calculated according to the EN-
14511 standard.
(3).
The seasonal coefficient for the cooling season (SEER) or the heating season (SCOP) has been calculated according to the EN-
14825 standard.
The seasonal area cooling performance ratio (
ηs,c) has been calculated according to the (EU) 2281 regulation.
(4).
Nominal heating capacity calculated according to the UNE-EN-14511 standard for indoor temperature of 20ºC and outdoor
temperature of 7ºC B.S. / 6ºC BH. Frequency of the compressor as stated above.
(5).
GWP: Global warming potential (climatic) of 1 kg of greenhouse gas for 1 kg of CO2, calculated over a period of 100 years.