SJ100 Inverter
Oper
ations
and Monitor
ing
4–29
Output Deviation for PID Control
The PID loop error is defined as the
magnitude (absolute value) of the differ-
ence between the Setpoint (target value)
and the Process Variable (actual value).
When the error magnitude exceeds the
preset value for C_44, the [OD] terminal
signal turns ON. Refer to
NOTE:
The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter’s output transistor.
[OD]
Signal
SP, PV
C 44
C 44
1
0
t
ON
ON
Setpoint
Process variable
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
04
OD
Output Deviation for
PID Control
ON
when PID error is more than the set threshold for
the deviation signal
OFF
when PID error is less than the set threshold for
the deviation signal
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
C_44
Notes:
•
The default difference value is set to 3%. To change
this value, change parameter C_44 (deviation
level).
RY
+
–
12 11
L
H O OI
FM CM2
Example (requires output configuration—
see page
):
Inverter output
terminal circuit
See I/O specs on page
OD