SJ100 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–31
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
B_81 [FM] terminal analog
meter adjustment
Adjust 8-bit gain to analog
meter connected to terminal
[FM], range is 0 to 255
✔
80
80
80
—
ADJ 080
B_82 Start frequency adjust-
ment
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
✘
0.5
0.5
0.5
Hz
Fmin 0.5Hz
B_83 Carrier frequency
setting
Sets the PWM carrier (internal
switching frequency), range is
0.5 to 16.0 kHz
✘
5.0
5.0
12.0
kHz
CARRIER 05.0kHz
B_84 Initialization mode
(parameters or trip
history)
Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
✘
00
—
INIT MODE TRP
B_85 Country code for initial-
ization
Select default parameter values
for country on initialization,
four options, option codes:
00... Japan version
01... Europe version
02... US version
03... reserved (do not set)
✘
01
02
00
—
INIT SEL USA
B_86 Frequency scaling
conversion factor
Specify a constant to scale the
displayed frequency for D_07
monitor, range is 0.1 to 99.9
✘
1.0
1.0
1.0
—
/Hz01.0 0.00
B_87 STOP key enable
Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
✘
00
00
00
—
STOP-SW ON