Network Variables and Setting (HARC70-CE1 OP)
Water
Cooled
Condenser
less
Air
Cooled
Air Heat
Pump
SVNT
Number
Name
Type
LONMARK
SNVT No
Description
Contents
Remarks
O
O
O
O
nv0
nviChillerEnable_0
SNVT_switch
95
On/Off Order
Byte 1: Value 0 (Fixed)
Byte 2: State 0/1 = STOP/RUN
Provide an interval
of 5 seconds of
more between
each setting
O
O
O
O
nv1
nviCoolSetpt
SNVT_temp_p
105
Cool Water Temperature
Setting
2 Bytes: -2000 ~ 2500 = -20 ~ 25 ºC
O
O
O
O
nv2
nviMode
SNVT_hvac_mode
108
Operation Mode Setting
1 byte:
1 = HVAC_HEAT (Heating)
3 = HVAC_COOL (Cooling)
-
-
-
O
nv3
nviHeatSetpt
SNVT_temp_p
105
Hot Water Temperature
Setting
2 bytes: 3000 ~ 6000 = 30 ~ 60 ºC
O
O
O
O
nv4
nvoOnOff
SNVT_switch
95
On/Off state
Byte 1: Value 0 (Fixed)
Byte 2: State 0/1 = STOP/RUN
Those values are
updated each 60
seconds.
When setting
points are changed
from HARC
change to related
point is detected
not waiting 60
seconds.
If no water chiller
is connected these
values are set to 0
O
O
O
O
nv5
nvoActiveSetpt
SNVT_temp_p
105
Temperature Setting
2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC
-
-
-
-
nv6
nvoActualCapa
SNVT_lev_percent
(Not Available)
81
Operation Capacity (Not
used for continous capacity) NOT USED
O
O
O
O
nv7
nvoLvgCHWTemp
SNVT_temp_p
105
Chilled outlet temperature
2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC
O
O
O
O
nv8
nvoEntCHWTemp
SNVT_temp_p
105
Chilled inlet temperature
2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC
O
O
O
O
nv9
nvoAlarmDescr
SNVT_str_asc
36
Alarm code
31 Bytes: 4 first bytes alarm description
as shown in chiller. 5th byte always 0.
Others undefined
O
O
O
O
nv10
nvoChillerStat
SNVT_chlr_status
127
Chiller Status
3 bytes:
Byte 1: Chiller Run Mode
0: Chlr_Off (OFF Mode) 2:Chlr_Run
(Run Mode)
Byte 2: Chiller Operation Mode
1: HVAC_HEAT (Heating) 3:HVAC_COOL
(Cooling)
A: HVAC_FREE_COOL (Cooling
Thermostat Off)
Byte 3: Chlr State
bit 0: 0/1 (no alarm / alarm)
bit 1: 0/1 (run not available / run available)
bit 2: 0/1 (central / local)
bits 3 ~ 7: Not used
O
O
O
O
n11
nvoDpress1
SNVT_press
30
Discharge Pressure 1
2 Bytes:0~30000 = 0~3,000 kPa
O
O
O
O
n12
nvoDpress1
SNVT_press
30
Discharge Pressure 2
2 Bytes:0~30000 = 0~3,000 kPa
O
-
O
-
n13
nvoDpress1
SNVT_press
30
Discharge Pressure 3
2 Bytes:0~30000 = 0~3,000 kPa
O
-
O
-
n14
nvoDpress1
SNVT_press
30
Discharge Pressure 4
2 Bytes:0~30000 = 0~3,000 kPa
-
-
O
-
n15
nvoDpress1
SNVT_press
30
Discharge Pressure 5
2 Bytes:0~30000 = 0~3,000 kPa
-
-
O
-
n16
nvoDpress1
SNVT_press
30
Discharge Pressure 6
2 Bytes:0~30000 = 0~3,000 kPa
O
O
O
O
n17
nvoSpress1
SNVT_press
30
Suction Pressure 1
2 Bytes:0~30000 = 0~3,000 kPa
O
O
O
O
n18
nvoSpress2
SNVT_press
30
Suction Pressure 2
2 Bytes:0~30000 = 0~3,000 kPa
O
-
O
-
n19
nvoSpress3
SNVT_press
30
Suction Pressure 3
2 Bytes:0~30000 = 0~3,000 kPa
O
-
O
-
n20
nvoSpress4
SNVT_press
30
Suction Pressure 4
2 Bytes:0~30000 = 0~3,000 kPa
-
-
O
-
n21
nvoSpress5
SNVT_press
30
Suction Pressure 5
2 Bytes:0~30000 = 0~3,000 kPa
-
-
O
-
n22
nvoSpress6
SNVT_press
30
Suction Pressure 6
2 Bytes:0~30000 = 0~3,000 kPa
O
O
O
O
n23
nvoDtemp1
SNVT_temp_p
105
Discharge Temp 1
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
O
O
O
n24
nvoDtemp2
SNVT_temp_p
105
Discharge Temp 2
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
-
n25
nvoDtemp3
SNVT_temp_p
105
Discharge Temp 3
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
-
n26
nvoDtemp4
SNVT_temp_p
105
Discharge Temp 4
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
O
-
n27
nvoDtemp5
SNVT_temp_p
105
Discharge Temp 5
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
O
-
n28
nvoDtemp6
SNVT_temp_p
105
Discharge Temp 6
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
O
O
O
n29
nvoSTemp1
SNVT_temp_p
105
Suction Temp 1
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
O
O
O
n30
nvoSTemp2
SNVT_temp_p
105
Suction Temp 2
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
-
n31
nvoSTemp3
SNVT_temp_p
105
Suction Temp 3
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
-
n32
nvoSTemp4
SNVT_temp_p
105
Suction Temp 4
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
O
-
n33
nvoSTemp5
SNVT_temp_p
105
Suction Temp 5
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
O
-
n34
nvoSTemp6
SNVT_temp_p
105
Suction Temp 6
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
O
O
n35
nvoODtemp
SNVT_temp_p
105
Outdoor Temperature
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
O
O
O
n36
nvoCompOnOff1
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
O
O
O
O
n37
nvoCompOnOff2
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
O
-
O
-
n38
nvoCompOnOff3
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
O
-
O
-
n39
nvoCompOnOff4
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
-
-
O
-
n40
nvoCompOnOff5
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
-
-
O
-
n41
nvoCompOnOff6
SNVT_state x 16
83
Compressor Information
32 Bytes: Byte 1: b0: 0/1 = STOP/RUN
O
O
O
O
n42
nvoLvgCHWTemp1 SNVT_temp_p
105
Outlet Water Temp 1
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
O
n43
nvoLvgCHWTemp2 SNVT_temp_p
105
Outlet Water Temp 2
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
O
-
n44
nvoLvgCHWTemp3 SNVT_temp_p
105
Outlet Water Temp 3
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
O
-
-
n45
nvoLvgCHWTemp4 SNVT_temp_p
105
Water Temp in Cooler
BackSide 1
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
-
-
n46
nvoLvgCHWTemp5 SNVT_temp_p
105
Water Temp in Cooler
BackSide 2
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
O
-
-
-
n47
nvoLvgCHWTemp6 SNVT_temp_p
105
Water Temp in Cooler
BackSide 3
2 Bytes: -12700 ~12700 = -127 ~ 127 ºC
-
-
-
-
n48
unused 1
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n49
unused 2
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n50
unused 3
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n51
unused 4
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n52
unused 5
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n53
unused 6
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n54
unused 7
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n55
unused 8
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
-
-
-
-
n56
unused 9
SNVT_temp_p
105
NOT USED
NOT USED
NOT USED
O
O
O
O
nv57
nciMaxSendTime
O
O
O
O
nv58
nciMinSendTime
NOTE:
Set and use the variables in accordance with the above tables. (The variables based on “Chiller Part of LonMark
Function
Profile”, however, some function and setting range have limitation).
Summary of Contents for SAMURAI CLG2
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 46: ......
Page 62: ......
Page 66: ......
Page 82: ......
Page 94: ...Drawings Technical Catalogue TCGB0051 rev 0 09 2009 94 14 2 4 Main printed circuit board ...
Page 95: ...Drawings Technical Catalogue 14 95 TCGB0051 rev 0 09 2009 14 2 5 Relays printed circuit board ...
Page 98: ......
Page 112: ......
Page 116: ......
Page 117: ......