UNITS INSTALLATION
3
- Service Access Panel
Provide a service access door or panel as shown
below.
(Space
around
Indoor
Unit)
(mm)
Size
A
B
Model
RPF
RPFI
RPF
RPFI
1.0
1.5
1479 1359
2.0
2.5
630 620
1729 1609
-
Consider the air distribution from the indoor unit to the
space of the room, and select a suitable location so that
uniform air temperature in the room can be obtained.
-
Check to ensure that the foundation is flat, level and
sufficiently strong.
-
It is recommended that a service access panel for floor
concealed type indoor units be provided. The access
panel must be fixed with screw(s) so that service
engineer(s) only is accessible.
2.1.3.
INSTALLATION
1. Check to ensure the fixing position of the unit as shown
below.
(mm)
Model
A
B
C
D
E
F
G
RPF-1.0 1045
754 732
RPF-1.5
1170 879
217
857
228 140 630
RPFI-1.0
863 754
732
RPFI-1.5
988 879
66
857
77 138 620
RPF-2.0
RPF-2.5
1420
1129 11 1107 228 140 630
RPFI-2.0
RPFI-2.5
1234 1129 11 1107 53 139 620
2. Adjust the flat level of the unit by adjusting bolts for
installation which are attached in the unit. Make the
drain pipe side lower than the opposite side for smooth
drain.
3. Fix the base plate and back plate of the unit with field-
supplied fixing bolts and screws. When attaching the
adjusting bolts for installation, remove the electrical
wiring box.
4. In case of the RPF unit, perform the above work after
removing the front cover and side cover of the unit.
5. Install the optional air outlet grille of the RPFI unit as
shown in the following figure. If installed in a
comparatively high humid place, condensation may
occur. Therefore, attach a plate which can absorb
water, like SUNKEN AQ made by ASAHI Chemical Co.,
around the grille.
¬
WARNING:
Provide a service access cover which is fixed by
screws so that the fan runner is not directly touched
(Only RPFI model).
CAUTION:
The optional air outlet grille of the RPFI unit can not
be used in a highly humid place like a kitchen,
because condensation may occur on the grille
surface.
Air Outlet Direction Change (RPFI)
In case of changing the RPFI units air outlet direction from
upward to front, follow the procedures below.
1. Remove the fixing screws of the air outlet flange and the
up-front cover. Then, remove the flange and the cover.
2. Reverse the side of the flange right and left.
3. Put the cover on the top of the unit, and put the flange
on the front side of the unit.
4. Fix the flange and the cover.
Optional Location for PC-ART (RPF)
In case of RPF unit, it is possible to install the PC-ART
under the plastic cover as show in the following figure.
RUN/STOP
TEMP
Unit
(Inside)
Service Access Panel
Service
Access Panel
B
A
Floor
Fixing onto Floor using wood screws
(2-M8) (View from top Side)
Fixing onto Wall
(View from front Side)
Fixing onto Floor using
wood screws (4-M5)
(View from top Side)
Side Cover
Fixing Bolt
Fixing Bolt
Adjustment Bolt for
Installation (Accessories)
Front Cover
Fixing screw
Air Outlet Flange
Absorbent Plate for Water
Ex.: SUNFINE AQ made by ASAHI
Chemical Co.
Polyurethane Foam for Thermal
Insulation (Field-Supplied)
Air Outlet Duct (Field-Supplied)
Floor Concealed Unit
Fix PC-ART by using 2 screws
(factory Supplied)