3. Servicing
Cycle components
SMGB0082 rev.1 - 07/2015
87
3
3.5.4
Replacement of the Brazed plate heat exchanger
Remove the rear panel as detailed in chapter
“3.4.5 Rear cover (water connection side)”.
Remove the water pipes support as described in section
1
Remove the thermistors THMr2 as explained in
chapter
““3.5.19 Replacement of the thermistor
Thermistor THMr2(x2)
Evaporation pipe
2
Remove the thermistor THMwo2 as explained in
chapter
“3.5.21 Thermistor (Cooler water outlet,
Thermistor THMwo2
3
Remove the 2 flare nuts from the refrigerant cir
-
cuit.
Flare nuts (x2)
4
Remove the 4 screws and their assemblies from
the suction pipe.
Bolt
Flange plate
Spring washer
Gasket
Flat washer
Bolt (x4)