4. Troubleshooting
Troubleshooting by alarm code
SMGB0082 rev.1 - 07/2015
138
Alarm code
C1-39
Current sensor abnormality (CN36)
Alarm stop reason
Current sensor indicates an abnormal value (CT).
PCB monitoring position
PCBd (I/O PCB) CN36 (Current sensor (CT))
Revision of connections
Revision of connections
Revision of wiring
Replacement of current
sensor
Check of current sensor
specifications. Check of
DIP switches
Yes
Yes
Yes
No
No
No
No
Yes
The connection and insertion of connector
CN36 on PCBd (I/O PCB) is correct
The connection and insertion of the
connector of current sensor on the body of the
unit are correct
There are no changes to the characteristics
of the current sensor (The characteristics of the
current sensor differ in standard specification and
special voltage specification)
The power wiring of compressor passes
through the current sensor
Alarm code
C1-f0
Setting of number of Fan units
Alarm stop reason
Fan is asked to operate when all fan manual set switches are set to OFF.
PCB monitoring position
PCBd (I/O PCB) DSW1-1 to 4: ON
Set DSW correctly
Replace PCBd (I/O PCB)
Yes
No
The connection and insertion of connector
CN31Pd on PCBd (I/O PCB) are correct
Alarm code
C1-F1
Fan overcurrent relay
Alarm stop reason
PCBd (I / O board) PCN210 short circuit line break.
PCB monitoring position
PCBd(I / O board) PCN210 (short line)
Revision of connections
Check PCBd (I/O PCB)
Yes
No
The connection and insertion of connector
PCN210 on PCBd (I/O PCB) are correct