3. Servicing
Cycle components
SMGB0082 rev.1 - 07/2015
96
3.5.20
Replacement of the thermistor (Cooler water inlet, THMwi)
1
Unscrew the nut of the cable gland
2
Gently pull the sensor wiring upwards.
C A U T I O N
Sensor sheath is full of sealing silicone. Use gloves
and eye goggles for protection in order to avoid
possible injuries to eyes and skin.
3
Disconnect the 1A and 1B Faston terminals at
the QCN3 connector at the rear of the E-box
4
Replace the thermistor in reverse order than re-
moving.
N O T E
Use sealant silicone inside the sensor sheath to
protect and avoid any leakage.
Cable gland
Fitting adaptor
Sensor sheath
Sensor
Sensor wiring
Thermistor THMwi
3.5.21
Thermistor (Cooler water outlet, THMwo2)
1
Unscrew the nut of the cable gland
2
Gently pull the sensor wiring upwards.
C A U T I O N
Sensor sheath is full of sealing silicone. Use gloves
and eye goggles for protection in order to avoid
possible injuries to eyes and skin.
3
Disconnect the 3C and 3D Faston terminals at
the QCN3 connector from the rear of the E-box.
4
Replace the thermistor in reverse order than re-
moving.
N O T E
Use sealant silicone inside the sensor sheath to
protect and avoid any leakage.
Thermistor THMwo2
Cable gland
Fitting adaptor
Sensor sheath
Sensor
Sensor wiring