3 Piping work and
refrigerant charge
95
3
SMGB0077 rev.0 - 01/2013
3.3 General instructions on the installation of refrigerant pipes
The copper pipe used for the installation must be specific for refrigeration systems as is indicated in section Copper pipes
and sizes.
The diameter of the refrigerant pipes depends directly on the power of the outdoor unit. The pipe diameter allocated must
be respected, in line with the instructions given in chapter Refrigerant pipe selection.
The location of the units and the pipe layout must be carried out in line with the instructions given in the Service Manual
corresponding to the outdoor units of the UTOPIA or SET FREE systems, especially when the outdoor unit is situated at a
different height than the indoor units.
System performance depends on the distance between the outdoor and indoor unit. This aspect must be taken into
account for the installation of the refrigerant pipe. The outdoor units are factory-charged with sufficient refrigerant for
a standard installation of certain characteristics. Where the system installation requirements involve an increase in the
distance between the outdoor and indoor unit, refrigerant must be added to the installation in line with the instructions
given in the Technical Catalogue and the Service Manual corresponding to the outdoor units of the UTOPIA or SET FREE
systems.
Summary of Contents for RCD-2.5FSN2
Page 2: ......
Page 4: ...SMGB0077 rev 0 01 2013 IV Index ...
Page 12: ...TCGB0077 rev 0 01 2013 XII Index ...
Page 24: ......
Page 102: ...2 Unit installation 90 SMGB0077 rev 0 01 2013 ...
Page 180: ...4 Electrical wiring 168 SMGB0077 rev 0 01 2013 Wiring diagrams for RCIM 0 8 2 0 FSN2 ...
Page 191: ...4 Electrical wiring 179 4 SMGB0077 rev 0 01 2013 DX Interface EXV 2 0 10 0 E1 ...
Page 192: ...4 Electrical wiring 180 SMGB0077 rev 0 01 2013 ...
Page 218: ......
Page 264: ...7 Test run 252 SMGB0077 rev 0 01 2013 ...
Page 276: ...9 Spare parts 264 SMGB0077 rev 0 01 2013 9 1 RCI 1 0 6 0 FSN3 SPN201201 ...
Page 278: ...9 Spare parts 266 SMGB0077 rev 0 01 2013 9 2 RCI 1 0 1 6 FSN3Ei EPN 201204A ...
Page 282: ...9 Spare parts 270 SMGB0077 rev 0 01 2013 9 4 RCD 1 0 3 0 FSN2 ...
Page 284: ...9 Spare parts 272 SMGB0077 rev 0 01 2013 9 5 RCD 4 0 5 0 FSN2 ...
Page 286: ...9 Spare parts 274 SMGB0077 rev 0 01 2013 9 6 RPC 2 0 6 0 FSN2E ...
Page 288: ...9 Spare parts 276 SMGB0077 rev 0 01 2013 9 7 RPI 0 8 1 5 FSN4E ...
Page 290: ...9 Spare parts 278 SMGB0077 rev 0 01 2013 9 8 RPI 2 0 3 0 FSN4E EPN 201208A 1B ...
Page 292: ...9 Spare parts 280 SMGB0077 rev 0 01 2013 9 9 RPI 4 0 6 0 FSN4E EPN 201208A 2B ...
Page 294: ...9 Spare parts 282 SMGB0077 rev 0 01 2013 9 10 RPI 8 0 10 0 FSN3E EPN 201108A 1B ...
Page 296: ...9 Spare parts 284 SMGB0077 rev 0 01 2013 9 11 RPIM 0 8 1 5 FSN4E DU EPN 201206A 2B ...
Page 298: ...9 Spare parts 286 SMGB0077 rev 0 01 2013 9 12 RPK 0 8 1 0 FSN H 3M ...
Page 300: ...9 Spare parts 288 SMGB0077 rev 0 01 2013 9 13 RPK 1 5FSN H 3M ...
Page 302: ...9 Spare parts 290 SMGB0077 rev 0 01 2013 9 14 RPK 2 0 4 0 FSN3M ...
Page 304: ...9 Spare parts 292 SMGB0077 rev 0 01 2013 9 15 RPF 1 0 2 5 FSN2E ...
Page 306: ...9 Spare parts 294 SMGB0077 rev 0 01 2013 9 16 RPFI 1 0 2 5 FSN2E ...
Page 308: ...9 Spare parts 296 SMGB0077 rev 0 01 2013 9 17 KPI 252 2002 E H 3E and KPI 502 1002 X3E ...
Page 310: ...9 Spare parts 298 SMGB0077 rev 0 01 2013 9 18 DX Interface ...