3 Piping work and
refrigerant charge
93
3
SMGB0077 rev.0 - 01/2013
3.2 Copper pipes, sizes, connection and insulation
3.2.1
Copper pipes and sizes
C A U T I O N
•
The copper pipe used in the refrigeration installations is different to the copper pipe used in installations
carrying domestic or heating water.
•
The copper pipe for refrigeration installations is especially treated for outdoors and indoors. The interior
surface finish makes it easier for the refrigerant to circulate and withstands the action of the lubricant oil
applied to outdoor equipment.
Prepare the copper pipes provided by the supplier.
Select the pipe with the appropriate diameter and thickness. Use the table below to select the most appropriate pipe:
Nominal diameter
Thickness mm
Supply
mm
Inches
Ø6.35
1/4
0.80
Roll
Ø9.52
3/8
0.80
Roll
Ø12.7
1/2
0.80
Roll
Ø15.88
5/8
1.00
Roll
Ø19.05
3/4
1.00
Pipe
Ø22.20
7/8
1.00
Pipe
Ø25.40
1
1.00
Pipe
Ø28.60
1-1/8
1.00
Pipe
Always use clean copper pipes with no signs of knocks or cracks. Make sure there is no dust or dampness on the inside.
Before you install the pipes, clean the inside with oxygen-free nitrogen gas to eliminate any remains of dust or other
substances.
C A U T I O N
•
Do not use hand saws, circular saws, abrasive grinders or other tools that generate shavings.
•
Strictly follow national or local regulations regarding occupational health and safety.
•
Wear appropriate means of protection during cutting or brazing operations and installation (gloves, eye
protection, etc).
On completing the installation of the refrigerant pipes -B-, insulate
them appropriately using suitable insulating material -A- and seal
the open space between the holes made and the pipe, as shown
in the figure.
A
A
B
Summary of Contents for RCD-2.5FSN2
Page 2: ......
Page 4: ...SMGB0077 rev 0 01 2013 IV Index ...
Page 12: ...TCGB0077 rev 0 01 2013 XII Index ...
Page 24: ......
Page 102: ...2 Unit installation 90 SMGB0077 rev 0 01 2013 ...
Page 180: ...4 Electrical wiring 168 SMGB0077 rev 0 01 2013 Wiring diagrams for RCIM 0 8 2 0 FSN2 ...
Page 191: ...4 Electrical wiring 179 4 SMGB0077 rev 0 01 2013 DX Interface EXV 2 0 10 0 E1 ...
Page 192: ...4 Electrical wiring 180 SMGB0077 rev 0 01 2013 ...
Page 218: ......
Page 264: ...7 Test run 252 SMGB0077 rev 0 01 2013 ...
Page 276: ...9 Spare parts 264 SMGB0077 rev 0 01 2013 9 1 RCI 1 0 6 0 FSN3 SPN201201 ...
Page 278: ...9 Spare parts 266 SMGB0077 rev 0 01 2013 9 2 RCI 1 0 1 6 FSN3Ei EPN 201204A ...
Page 282: ...9 Spare parts 270 SMGB0077 rev 0 01 2013 9 4 RCD 1 0 3 0 FSN2 ...
Page 284: ...9 Spare parts 272 SMGB0077 rev 0 01 2013 9 5 RCD 4 0 5 0 FSN2 ...
Page 286: ...9 Spare parts 274 SMGB0077 rev 0 01 2013 9 6 RPC 2 0 6 0 FSN2E ...
Page 288: ...9 Spare parts 276 SMGB0077 rev 0 01 2013 9 7 RPI 0 8 1 5 FSN4E ...
Page 290: ...9 Spare parts 278 SMGB0077 rev 0 01 2013 9 8 RPI 2 0 3 0 FSN4E EPN 201208A 1B ...
Page 292: ...9 Spare parts 280 SMGB0077 rev 0 01 2013 9 9 RPI 4 0 6 0 FSN4E EPN 201208A 2B ...
Page 294: ...9 Spare parts 282 SMGB0077 rev 0 01 2013 9 10 RPI 8 0 10 0 FSN3E EPN 201108A 1B ...
Page 296: ...9 Spare parts 284 SMGB0077 rev 0 01 2013 9 11 RPIM 0 8 1 5 FSN4E DU EPN 201206A 2B ...
Page 298: ...9 Spare parts 286 SMGB0077 rev 0 01 2013 9 12 RPK 0 8 1 0 FSN H 3M ...
Page 300: ...9 Spare parts 288 SMGB0077 rev 0 01 2013 9 13 RPK 1 5FSN H 3M ...
Page 302: ...9 Spare parts 290 SMGB0077 rev 0 01 2013 9 14 RPK 2 0 4 0 FSN3M ...
Page 304: ...9 Spare parts 292 SMGB0077 rev 0 01 2013 9 15 RPF 1 0 2 5 FSN2E ...
Page 306: ...9 Spare parts 294 SMGB0077 rev 0 01 2013 9 16 RPFI 1 0 2 5 FSN2E ...
Page 308: ...9 Spare parts 296 SMGB0077 rev 0 01 2013 9 17 KPI 252 2002 E H 3E and KPI 502 1002 X3E ...
Page 310: ...9 Spare parts 298 SMGB0077 rev 0 01 2013 9 18 DX Interface ...