background image

   

CAUTION

·

Air

 

Tight Check - Do use Nitrogen. 

 6. Vacuum Pumping and Refrigerant Charge

·

Vacuum

 

Pumping

 

Air Tight  Procedure

Completion

of

 

Ref

.

Piping

Repairing

of

 

Leakage

Part

Check

 

of

Pressure

Decrease

Applying
Nitrogen

Gas

Pass

Procedure

Connect the gauge manifold using charging hoses with a nitrogen
cylinder to the check joints of the liquid line and the gas line stop 
valves. 
Perform the air tight test.
Don't open the gas line stop valves.
Apply nitrogen gas pressure of 550 psig (3.8 MPa).
Check for any gas leakage at the flare nut connections, or brazed 
parts by gas leak detector or foaming agent. 
Gas pressure doesn’t decrease, which is OK.
After the air tight test, release nitrogen gas.

 ·

An

 

excess

 

or

 

a

 

shortage

 

of

 

refrigerant

 

is

 

the

 

main cause

 

of

 

trouble

 

to

 

the

 

unit

Charge

 

the

 

correct

 

quantity

 

of

 

      refrigerant

 

according to

 

the

 

description

 

in the

 

manual

.

 ·

Check

 

for

 

refrigerant

 

leakage

 

in

 

detail

If

 

a

 

large refrigerant

 

leakage

 

occurs

it

 

will

 

cause

 

difficulty in

 

breathing

 

or

 

      harmful

 

gases

 

would

 

occur

 

if

 

a fire

 

is

 

being

 

used

 

in

 

the

 

room

.

Charge hose
(for R410A)

Installation instructions

 Piping insulation procedure

Insulation

(

)

field-supplied

(6) After finishing connecting the refrigerant pipes, keep it warm with 
     the insulation material.

·

For outdoor unit side, surely insulate every piping including valves.

·

Cover piping joints with pipe cover.

·

Using piping tape, apply taping starting from the entry of outdoor unit. 

   

-

 Fix the end of piping tape with adhesive tape.

   -

 When piping has to be arranged through above ceiling, closet or area

    where temperature and humidity are high, wind additional commercially
    sold insulation for prevention of condensation.

 5. Air

 

Tight Test

Clamp (field-supplied) Insulation (field-supplied)

Refrigerant pipe

(field-supplied)

  (1) Remove the service port cap of  the stop valve on the gas pipe 
       side of the outdoor unit.     
  (2) Connect the manifold gauge and vacuum pump to the service port 
       of the stop valve on the gas pipe side of the outdoor unit.
  (3) Run the vacuum pump. (Work for more than 15 minutes.)
  (4) Check the vacuum with the gauge manifold valve, then close the
       gauge manifold valve and stop the vacuum pump.
  (5) Leave it as is for one or two minutes. Make sure that the pointer of 
       the manifold gauge remains in the same position. Confirm that the 
       pressure gauge shows -14.7psig (-0.101MPa or -760mmHg).
  (6) Remove the manifold gauge quickly from the service port of the 
       stop valve.
  (7)

 

After refrigerant pipes are connected and evacuated, fully open

        all stop valves on both sides of gas pipe and liquid pipe.
  (8) Open adjusted valve to add refrigerant 

(

the refrigerant

 

is

 

liquid

).

  (9) Tighten the cap to the service port .
  (10) Retighten the cap.
  (11) Leak test foam with halogen leak detector to check the flare nut 
         and brazing Carolina Department leaks. Use foam that does not 
         generate ammonia (NH3) in the reaction.
  

 8

Indoor unit

Outdoor unit

Manifold 

valve

Pressure

gauge

Vacuum 

pump

Summary of Contents for RAS-1.0PNNBDH1

Page 1: ... RAS 1 0PNNBDH1 RAS 1 5PNNBDH1 RAS 2 0PNNBDH1 RAS 3 0PNNBDH1 RAS 4 0PNNBDH1 OUTDOOR UNITS DC INVERTER SERIES HO2021388HA ...

Page 2: ... is designed for the following temperatures It should be operated within this range DC Inverter Unitary Series Mode Outdoor Operation Temperature Range Model Maximum Minimum Cooling Operation 1 0 4 0HP 9K 36K 118 48 5 15 Heating Operation 3 0HP 24K 75 24 13 25 1 0 1 5 2 0 4 0HP 9K 12K 18K 36K 75 24 4 20 Storage Condition Temperature 13 140 25 60 Humidity 30 80 The numbers in the model represent th...

Page 3: ...tance with no connection and don t connect multiple devices to the same AC power supply Otherwise it may result in bad contact poor insulation unallowable current which could finally result in fire or electric shock After all installations are completed check to make sure that no refrigerant leakage occurs It will generate harmful substances if the refrigerant gas leaks in the interior area and ha...

Page 4: ...onditions and these means must be incorporated in the fixed wiring in accordance with the wiring rules If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The appliance shall be installed in accordance with national wiring regulations Servicing shall only be performed as recommended by the equipment manuf...

Page 5: ...hanger EEV Service valve Electrical Wiring Diagram Refrigerant Flow Diagram Outdoor Unit Indoor Unit Terminal Terminal Power Supply Power Connecting Cord 1 0 1 5 2 0 3 0 4 0HP 9K 12K 18K 24K 36K SI SI L L N N L2 L1 NOTE Since there may be differences in some models terminal blocks wiring connection should be done according to letters on the terminal block Please disregard numbers in this case ...

Page 6: ...required for the affected device Install the unit horizontally Please install it in an area not affected by snowfall or blowing snow In areas with heavy snow please install a canopy a pedestal and or some baffle boards Avoid the following places for installation where air conditioner trouble is liable to occur Where there is much machine oil Salty places such as seaside Where sulfide gas is genera...

Page 7: ... avoid disturbing neighbors and to protect the environment it is necessary to install a drainage elbow and a drain hose to drain out the condensate water Please do the drainage work before the indoor unit and outdoor unit are connected Otherwise it will be difficult to install drainage elbow after the machine becomes immovable Connect the drain hose field supplied nside diameter i 5 8 in 15mm as s...

Page 8: ...itional refrigerant charge L 24 6 0 161 oz ft For 2 0 4 0HP 18K 36K Additional refrigerant charge L 24 6 0 376 oz ft Refrigerant Piping Model Outer Diameter of Pipe in mm Gas Liquid 1 0 1 5HP 9K 12K ø3 8 ø9 52 ø1 4 ø6 35 2 0HP 18K ø1 2 ø12 7 ø1 4 ø6 35 3 0HP 24K ø ø15 88 5 8 ø ø9 52 3 8 4 0HP 36K ø ø19 05 3 4 ø ø9 52 3 8 Pipe Length L Height Difference H Indoor Unit Outdoor Unit 3 Piping thickness...

Page 9: ... Good o 90 Burr Copper pipe Spare reamer Pipe cutter Flare nut Copper pipe Flaring tool Clutch type Wing nut type Die Copper pipe Flare nut Copper pipe Die York Smooth all around Inside is shining without any scratches 4 Piping Connection 1 Confirm that the valve is closed 2 Connect the indoor unit and the outdoor unit with field supplied refrigerant piping Suspend the refrigerant piping at certai...

Page 10: ... cover Using piping tape apply taping starting from the entry of outdoor unit Fix the end of piping tape with adhesive tape When piping has to be arranged through above ceiling closet or area where temperature and humidity are high wind additional commercially sold insulation for prevention of condensation 5 Air Tight Test Clamp field supplied Insulation field supplied Refrigerant pipe field suppl...

Page 11: ...rotect the wires electrical parts etc from rats or other small animals If not protected rats may gnaw at unprotected parts and at the worst a fire will occur Avoid the wiring from touching the refrigerant pipes plate edges and electrical parts inside the unit If not do the wires will be damaged and at the worst a fire will occur Install an ELB Electric Leakage Break in the power source If ELB is n...

Page 12: ...nd the transmitting cable to the conduit holder using the lock nut 3 Connect the power supply cable and the transmitting cable to terminal 4 Fasten the power supply cable and the transmitting cable with the cable clamp 5 Be sure to seal the holes when applying the putty Place the cables side to side Do not overlap the cables 6 Put the wiring distribution cover back after completion of the work Loc...

Page 13: ...e any trouble please contact local technical service center of our company for further information CAUTION Installation instructions Trial Run 11 NOTE 1 Follow local codes and regulations when selecting field wires and all the above are the minimum wire size 2 Use copper supply wires 3 When the transmitting cable is longer than 49 ft 15m a larger wire size should be selected 4 Install main switch ...

Page 14: ......

Page 15: ......

Page 16: ...ithout notice in order that Hitachi Johnson Controls Air Conditioning Inc may bring the latest innovations to their customers 2021 Johnson Controls Air Conditioning Inc Hitachi 2021 03 Version A Printed in China Hitachi Johnson Controls Air Conditioning Inc ...

Reviews: