2.2 The following is accessory parts of the outdoor unit. Please confirm it before installation.

  

 

Accessory 

Q

’ty 

Use Place 

Use Method 

Flange Combination

 

Use to connect gas 
piping. 

Please refer the piping work 
on page 9. 

Drain Connector 

Base condensation 
water exhaust. 

 

Please refer the foundation 
work on page 8. 

Washer 

Stop Gap Material 

 

  3. Before Installation 

 

3.1 The R410A refrigerant pressure higher than R22 about 1.4 times, it is more susceptible to moisture, acid materials, oil 

and other impurities influence. Because of the new refrigerant, refrigerant oil also will be changed. Therefore, when 

installation, be careful not to water, impurities, the existing use of the refrigerant and refrigeration oil mixed in the cycle 

system.

  

 

 

 

3.2 To avoid accidental mixing of different refrigerant or different refrigerant oil, the sizes of the charging connections have to 

be changed. It necessary to prepare the following special R410A tools before performing the installation work. 

The measuring machine or tool which will contact with the refrigerant, please use specially for the new 
refrigerant. 

Symbol Description

for new and old type refrigerant         

only for R410A(not for R22)         

only for R407C(not for R22)               

for two type R410A and R407C. 

Measuring Instrument and 

Tool 

Interchangeability 

with R22 

Reason of Non-Interchangeability and Attention   

(only for new refrigerant) 

(

Strictly Required) 

Use 

R407C  R410A 

Refrigerant 

Pipe

 

Pipe Cutter 

○ 

○ 

 

Cutting Pipe

Removing Burrs 

Flaring Tool 

○ 

○■ 

To ensure the high pressure of R410A, if using flaring 

tube, make the dimension of tube larger for R410A. If 
you continue to use existent products, shall be used with 
the flaring tube adjustment gasket (1mm). Using the 
1/2H pipe situation, can not be processed. 

(R410A special flaring tool can be used directly in the 

R407C)

 

Flaring for Tubes

 

Extrusion 
Adjustment 
Gauge 

─ 

(

not use

■ 

Dimensional Control for 
Extrusion Portion of Tube after 
Flaring

 

Pipe Bender 

○ 

○ 

Using the 1/2H pipe situation, can not be processed. 

Please use the elbow welding connection. 

Bending

 

Expanding Tool 

○ 

○ 

Using the 1/2H pipe situation, can not be processed. 

Please use the elbow welding connection.

 

Expanding Tubes

 

Torque Wrench 

○ 

■ 

R410A forΦ12.7

Φ15.88;spanner size is up 2mm; 

existent products can not be used.

 

Connection of Flare Nut

 

○ 

For Φ6.35

Φ9.53

Φ19.05; spanner size is the same. 

Brazing Tool 

○ 

○ 

Perform correct brazing work. 

Brazing for Tubes

 

Nitrogen Gas 

○ 

○ 

Strict control against contamination. 

(Blow nitrogen during brazing) 

Prevention from Oxidation 
during Brazing

 

Lubrication 
Oil(for Flare 
Surface) 

● 

■ 

 

Do not use R22 with mineral oil, and products must be 

used the same synthetic oil. 

Synthetic oil absorbs moisture quickly, Therefore, to avoid 

damp places. 

 

Applying Oil to the Flared 
Surface

 

Measuring Instrument and 

Tool 

Interchangeability 

with R22

 

Reason of Non-Interchangeability and Attention   

(only for new refrigerant) 

(

Strictly Required)

 

Use

 

R407C  R410A 

Vacuum 

Drying   

 

Refrigerant 

Change

 

Refrigerant 
Cylinder 

● 

(Brown) 

■ 

(Pink) 

Check refrigerant cylinder color.   

◎〈

  Filled with the gas refrigerant is strictly prohibited 

Liquid refrigerant charging is required regarding 
Non-azeotropic refrigerant.

 

Refrigerant Charging

 

Vacuum Pump 

○ 

○ 

The current ones are applicable. However, it is required 

to mount a vacuum pump adapter which can 

prevent 

from reverse flow 

when a vacuum pump stops, 

resulting in no reverse oil flow. 

Vacuum Pumping

 

Adapter for 
Vacuum Pump 

(prevent from 
reverse) 

※● 

■ 

The product of the design pressure is 4.15MpaG.

 

 

Summary of Contents for RAM-200FPS

Page 1: ...y or death Enforcement matters Machine with a ground terminal the user must follow the instructions for ground work Prohibitions Enforcement matters Indicating the general behavior Non specific object About electrical works DANGER When perform electrical work please have a qualified personnel Please note that the construction is not completely by yourself there will be occurred an electric shock P...

Page 2: ... system which all indoor units are operated simultaneously the total indoor unit capacity should be less or equal to the outdoor unit capacity For the system which all indoor units are not operated simultaneously the total indoor unit capacity is available up to maximum against the outdoor unit capacity 1 2 Operation temperature range Condition Item Air inlet temperature of outdoor unit Air inlet ...

Page 3: ... shall be used with the flaring tube adjustment gasket 1mm Using the 1 2H pipe situation can not be processed R410A special flaring tool can be used directly in the R407C Flaring for Tubes Extrusion Adjustment Gauge not use Dimensional Control for Extrusion Portion of Tube after Flaring Pipe Bender Using the 1 2H pipe situation can not be processed Please use the elbow welding connection Bending E...

Page 4: ...6 15 88 19 4 19 7 19 05 23 3 Can not be processed 1 2H material Please use the attached flare connecting pipe Pipe thickness selected With the design pressure changes the pipe thickness and material should also be changed Pipe Size Existent Type New Refrigerant R22 R407C R410A Thickness Material Thickness Material Thickness Material Φ6 35 0 6 O 0 8 O 0 8 O Φ9 53 0 8 O 0 8 O 0 8 O Φ12 7 0 8 O 0 8 O...

Page 5: ...is a high level of oil mist salty air or harmful gases such as sulphur 12 Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box 13 Install the outdoor unit as far as at least 3 meters from the electromagnetic wave radiator Strong wind blowing directly against the product installation method Installed on the roof and no buildings surrounding and t...

Page 6: ...ed 350 Above 300 Above 100 Above Front Side Note Must install the wind break cover plate Option and the both sides must be opened Note Must be opened on both sides A separate installation A row installation two more 350 Above 300 Below 350 Above 300 Below 1000 Above 350Above 1000 Above 100Above 350 Above Setting two sets situation 300 Below 100 Above 100Above 300 Below 1000 Above Front Side 350 Ab...

Page 7: ...sealed A separate installation A row installation two more Front Side 50Above 100Above 700 Above Note Must install the wind break cover plate Option and the both sides must one side be opened at least With the unit rear side same direction 350 Above 700Above Note Must install the wind break cover plate Option and the both sides must be opened 700Above 350Above 150 Above 700Above 100 Above A separa...

Page 8: ...t to withstand full weight of the outdoor unit 560 Hole 4 Φ16 x 23 5 Long Hole If ensure 170 dimension and without interference with foundation base it can be downward the piping work To avoid the unit vibration transmitted to the buildings if necessary to install anti vibration rubber Fixed Bracket Fielded supplied 21mm Below A After Cut Off Concrete Anchor Bolt Shelf Width 60 mm Standard Parts O...

Page 9: ... easy to produce powder Cautions for refrigerant piping work for example 2 Piping Direction The pipe can be connected in four directions Convex Drain Connector Washer Base Drain Hole When installing pipe through the wall Secure a cap at the end of the pipe Hole of wall Attach a cap or vinyl tape Attach a cap or vinyl tape Attach a cap or vinyl tape Do not place the pipe directly on the ground Rubb...

Page 10: ...lease make the gap of the upper A division remove part of piping In the unit s internal piping and wiring do not interfere with each other 2 3 Connection piping bending use the pipe bender 2 4 In order to metal plate s burrs does not hurt to wiring and piping Please use the insulation material Field supplied materials to protect them Open the service cover essentials 1 Please remove the left screw...

Page 11: ...m Piping Length Actual Length L1 L2 l 3 100m Below Equivalent Length L1 L2 l 3 120m Below The Total Length L1 L2 l0 l1 l2 l 3 250m Below Maximum Lift between Outdoor Unit and Indoor Unit The outdoor unit is higher than that of indoor unit H 1 40m Below The outdoor unit is lower than that of indoor unit H 1 30m Below Between each indoor unit H 2 15m Below Maximum Piping Length Between Each Multi ki...

Page 12: ...connected to the indoor unit be sure to use an optional parts of the multi kit pipe set in order to prevent the uneven distribution of the refrigerant and causing the unit s capacity reduction Do not connect using the connector 1 Line branch use the line branch pipe As shown below Main pipe The pipe between each multi kit pipe or the pipe between outdoor units to first multi kit pipe Main Branch T...

Page 13: ... Correct Setting Wrong Setting First Main Branch Second Main Branch First Branch Second Branch Third Branch First Main Branch Second Main Branch First Branch Second Branch Third Branch X Wrong Outdoor Outdoor Outdoor Outdoor First Main Branch First Main Branch Second Main Branch Second Main Branch First Branch First Branch Second Branch Second Branch Third Branch Third Branch X Wrong Fourth Branch...

Page 14: ...vibration of the piping Pay special attention in case of short piping length 4 Please perform the air tight test Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves Perform the air tight test Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit Do ...

Page 15: ...nt R410A which directly touch refrigerant 3 If vacuum degree of 0 1MPa 750mmHg is not available it is considered that leakage exists Check for any gas leakage once again If no leakage exists operate the vacuum pump for one to two hours 5 4 The Additional Refrigerant 1 Outdoor unit has been filled with refrigerant but still based on the length of pipe filled with an appropriate amount of refrigeran...

Page 16: ... will result in weight percent composition changes so can not directly add refrigerant treatment must be re processing system 5 6 Caution of Measure Pressure Data from The Check Joints Measure pressure data of work please from the check joints of gas line stop valve right figureⒶ and the check joints of piping line right figureⒷ to connect And then please according to the different operation state...

Page 17: ...Supply 3Φ 60Hz Maximum Current A ELB Earth Leakage Breaker Power Switch Power Supply Size mm2 Earth Wire Size mm2 Transmission Cable Size Number of Poles Rating Sensitivity Current mA Rating Current A Switch Capacity A Fuse Capacity A 1 2 2 3 4 5 RAM 200FPS 230V 22 3 30 30 60 30 3 5 5 5 2 Core Shielded Twist Pair Cable 0 75mm2 Total Length 1000m Below RAM 250FPS 29 40 40 5 5 RAM 270FPS 37 100 50 1...

Page 18: ...tion wiring construction The transmission cable of indoor and outdoor unit and the 220V power source cord be sure to keep the distance of more than 5 6cm Therefore do not use the coaxial cable If the transmission cable and power source cord connecting wrong will cause the PCB of the outdoor unit burning Please pay special attention 10 Indoor and outdoor unit s power source cord and connection wiri...

Page 19: ...gs shall be attached the insulation tape or insulation sleeve Χ Ο Fold the wire and reserve for a maintenance operation the desired length Prevent need to remove the wiring plug for maintenance Cord Band Operation 1 When wire through the cord band appropriately tighten it as show below 2 Make sure the cord with high and low pressure sensor isolation 3 Tighten the cord to be isolated with pipe comp...

Page 20: ...Do not input the power source to the terminal No 1 2 of transmission wiring 3 When power source wiring phase error the unit can not be operated and the remote controller display alarm code 05 At this time please refer to the electrical box caution nameplate check the phase of the first side and replace it The phase of the replacement work please process under the power source turn off 4 Does the o...

Page 21: ... operation 3 2 Depress RUN STOP switch The TEST RUN operation will be started The 2 hours OFF TIMER will be set and the TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again 3 3 To end the test run wait for 2 hours or push RUN STOP switch again Number of The Unit 0 1 2 3 4 10 11 63 Timer Setting Display Left Two Digit 01 02 03 04 05 11 12 64 Re...

Page 22: ...ity Low Pressure Thermistor Outdoor 31 System Incorrect Capacity Setting of Outdoor and Indoor Unit Incorrect Capacity Code Setting of Combination Excessive or Insufficient Indoor Unit Total Capacity Code outside of 80 120 35 Incorrect Setting of Indoor Unit No Duplication of Indoor Unit No In Same Ref Gr or The Connection Unit Number Exceeds The Maximum Number of Combination 38 Outdoor Unit Abnor...

Page 23: ...rigerant Temperature Operating Mode Cool Discharge Gas Temperature Td Liquid Pipe Temperature Te 8 Check Pressure Discharge Pressure Pd MPa Suction Pressure Ps MPa 9 Check Voltage Rated Voltage V Operating Voltage L1 L2 V L1 L3 V L2 L3 V Starting Voltage V Phase Imbalance 10 Check Compressor Input Running Current Input kW Running Current A A 11 Is the refrigerant charge adequate 12 Do the operatio...

Page 24: ...24 66MP1306 Printed in Philippines ...