Hitachi RAM-200FPS Installation & Maintenance Manual Download Page 22

22 

 

Alarm Code

 

 

Code 

Distinction 

Content of Abnormality 

Leading Cause 

01 

Indoor Unit 

Indoor Unit Activation of Protection Device(Float 
Switch) 

Activation of Float Switch (High water Level Drain Pan, Abnormality 
of Drain Pipe, Float Switch or Drain Pan) 

02 

Outdoor Unit 

Outdoor Unit Activation of Protection Device 

Activation of High Pressure Switch (4.15MPa); Air Conditioner 
Outdoor Unit Fan Motor Lock. 

03 

Wiring 

Transmission Abnormality between Indoor and 
Outdoor 

Incorrect Wiring, Loose Terminals, Disconnect Wire, Blowout of 
Fuse, Outdoor Unit Power OFF. 

04 

Inverter 

Transmission Abnormality between Inverter PCB 
and Outdoor PCB 

Inverter PCB - Outdoor PCB Transmission Failure (Loose 
Connector, Wire Breaking, Blowout of Fuse), Abnormal fan motor 
controller transmitted, "04" the lower right will be " . "Signal flashing. 

05 

Wiring 

Abnormality Power Source Phases 

Incorrect Power Source Phases, Connection to Reversed Phases, 
Open-Phases. 

06 

Voltage 

Abnormality Inverter Voltage 

Outdoor Voltage Drop, Insufficient Power Capacity. 

07 

Refrigerant 
Cycle System 

Decrease in Discharge Gas Superheat 

Excessive Refrigerant Charge, Failure of Thermistor, Incorrect 
Wiring, Incorrect Piping Connection, Expansion Valve Locking at 
Opened Position (Disconnect Connector). 

08 

Increase in Discharge Gas Temperature 

Insufficient Refrigerant Charge, Pipe Clogging, Failure of Thermistor, 
Incorrect Wiring, Incorrect Piping Connection, Expansion Valve 
Locking at Closed Position (Disconnect Connector). 

11 

Indoor Unit 
Thermistor   

Abnormality Inlet Air Thermistor (Indoor) 

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. 

12 

Abnormality Outlet Air Thermistor (Indoor) 

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. 

13 

Abnormality Freeze Protection Thermistor 
(Indoor) 

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. 

14 

Abnormality Gas Piping Thermistor (Indoor) 

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. 

19 

Activation of Protection for Indoor Fan Motor 

Fan Motor Overheat, Locking. 

21 

Outdoor Unit 
Thermistor 

Abnormality High Pressure Thermistor(Outdoor) 

Thermistor Incorrect Wiring, Disconnecting Wiring, Breaking Wire, 
Short Circuit. 

22 

Abnormality Outdoor Air Thermistor 

23 

Abnormality Discharge Pipe 
Thermistor(Outdoor) 

24 

Abnormality Heat Exchanger Liquid Pipe 
Thermistor(Outdoor) 

29 

Abnormality Low Pressure Thermistor (Outdoor) 

31 

System 

Incorrect Capacity Setting of Outdoor and Indoor 
Unit 

Incorrect Capacity Code Setting of Combination; Excessive or 
Insufficient Indoor Unit Total Capacity Code (outside of 80~120%) 

35 

Incorrect Setting of Indoor Unit No. 

Duplication of Indoor Unit No. In Same Ref. Gr., or The Connection 
Unit Number Exceeds The Maximum Number of Combination. 

38 

Outdoor Unit 

Abnormality of Picking Up Circuit for 
Protection(Outdoor) 

Failure of Protection Detecting Device(Incorrect Wiring of Outdoor 
PCB) 

43 

Pressure 

Activation of Low Pressure Decrease Protection 
Device 

Defective Compressor(Failure of Compressor of Inverter, Loose 
Power Supply Connection) 

44 

Activation of Low Pressure Increase Protection 
Device 

Overload at Cooling, High Temperature at Expansion Valve 
Locking(Loose Connector) 

45 

Activation of High Pressure Increase Protection 
Device 

Overload Operation (Clogging, Short-Pass), Pipe Clogging, 
Excessive Refrigerant, Inert Gas Mixing. 

47 

Activation of Low Pressure Decrease Protection 
Device(Vacuum Operation Protection) 

Insufficient Refrigerant, Pipe Clogging, Expansion Valve Locking at 
Open Position (Loose Connector). 

48 

Outdoor Unit 

Activation of Inverter Overcurrent Protection 
Device 

Overload Operation, Compressor Failure. 

51 

Inverter 

Abnormality Inverter Current Sensor 

Current Sensor Failure. 

53 

IPM Protection Activation 

Driver IC Error Signal Detection(Protection for Overcurrent, Low 
Voltage) 

54 

Activation of Inverter Fin Thermistor Protection 

Abnormality Fin Thermistor, Heat Exchanger Clogging, Fan Motor 
Failure. 

55 

Inverter Failure 

Inverter PCB Failure 

57 

Outdoor Unit 

Activation of Outdoor Fan Controller Protection  Abnormality Fan Controller Protection (Overcurrent),Fin Overheat 

EE 

Compressor 

Compressor Protection Alarm 

Compressor Occurred Three Times of Abnormality within 6 Hour. 

b1 

Wiring 

Incorrect Outdoor Unit Address Number or Unit 
Number Setting 

Over 64 Number Is Set for Address or Refrigerant Cycle. 

b5 

Number of Indoor Units Connected Error. 

Connection of Non-H-LINK-

  Indoor Unit More Than 17 Units. 

PS

Remote control operation indicator flashes once every 2 seconds, the symbol of between the indoor unit and remote control for the 

transmission abnormally (connector loss, loose, incorrect wiring, and disconnection).

 

4) Finally, please deliver the guarantee, operation manual, and installation manual, etc. to the customer to keep it. 
 

Danger

Before the preparation of test running, please do not start running, be sure implementation to confirm the electrical wiring, etc.

 

Summary of Contents for RAM-200FPS

Page 1: ...y or death Enforcement matters Machine with a ground terminal the user must follow the instructions for ground work Prohibitions Enforcement matters Indicating the general behavior Non specific object About electrical works DANGER When perform electrical work please have a qualified personnel Please note that the construction is not completely by yourself there will be occurred an electric shock P...

Page 2: ... system which all indoor units are operated simultaneously the total indoor unit capacity should be less or equal to the outdoor unit capacity For the system which all indoor units are not operated simultaneously the total indoor unit capacity is available up to maximum against the outdoor unit capacity 1 2 Operation temperature range Condition Item Air inlet temperature of outdoor unit Air inlet ...

Page 3: ... shall be used with the flaring tube adjustment gasket 1mm Using the 1 2H pipe situation can not be processed R410A special flaring tool can be used directly in the R407C Flaring for Tubes Extrusion Adjustment Gauge not use Dimensional Control for Extrusion Portion of Tube after Flaring Pipe Bender Using the 1 2H pipe situation can not be processed Please use the elbow welding connection Bending E...

Page 4: ...6 15 88 19 4 19 7 19 05 23 3 Can not be processed 1 2H material Please use the attached flare connecting pipe Pipe thickness selected With the design pressure changes the pipe thickness and material should also be changed Pipe Size Existent Type New Refrigerant R22 R407C R410A Thickness Material Thickness Material Thickness Material Φ6 35 0 6 O 0 8 O 0 8 O Φ9 53 0 8 O 0 8 O 0 8 O Φ12 7 0 8 O 0 8 O...

Page 5: ...is a high level of oil mist salty air or harmful gases such as sulphur 12 Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box 13 Install the outdoor unit as far as at least 3 meters from the electromagnetic wave radiator Strong wind blowing directly against the product installation method Installed on the roof and no buildings surrounding and t...

Page 6: ...ed 350 Above 300 Above 100 Above Front Side Note Must install the wind break cover plate Option and the both sides must be opened Note Must be opened on both sides A separate installation A row installation two more 350 Above 300 Below 350 Above 300 Below 1000 Above 350Above 1000 Above 100Above 350 Above Setting two sets situation 300 Below 100 Above 100Above 300 Below 1000 Above Front Side 350 Ab...

Page 7: ...sealed A separate installation A row installation two more Front Side 50Above 100Above 700 Above Note Must install the wind break cover plate Option and the both sides must one side be opened at least With the unit rear side same direction 350 Above 700Above Note Must install the wind break cover plate Option and the both sides must be opened 700Above 350Above 150 Above 700Above 100 Above A separa...

Page 8: ...t to withstand full weight of the outdoor unit 560 Hole 4 Φ16 x 23 5 Long Hole If ensure 170 dimension and without interference with foundation base it can be downward the piping work To avoid the unit vibration transmitted to the buildings if necessary to install anti vibration rubber Fixed Bracket Fielded supplied 21mm Below A After Cut Off Concrete Anchor Bolt Shelf Width 60 mm Standard Parts O...

Page 9: ... easy to produce powder Cautions for refrigerant piping work for example 2 Piping Direction The pipe can be connected in four directions Convex Drain Connector Washer Base Drain Hole When installing pipe through the wall Secure a cap at the end of the pipe Hole of wall Attach a cap or vinyl tape Attach a cap or vinyl tape Attach a cap or vinyl tape Do not place the pipe directly on the ground Rubb...

Page 10: ...lease make the gap of the upper A division remove part of piping In the unit s internal piping and wiring do not interfere with each other 2 3 Connection piping bending use the pipe bender 2 4 In order to metal plate s burrs does not hurt to wiring and piping Please use the insulation material Field supplied materials to protect them Open the service cover essentials 1 Please remove the left screw...

Page 11: ...m Piping Length Actual Length L1 L2 l 3 100m Below Equivalent Length L1 L2 l 3 120m Below The Total Length L1 L2 l0 l1 l2 l 3 250m Below Maximum Lift between Outdoor Unit and Indoor Unit The outdoor unit is higher than that of indoor unit H 1 40m Below The outdoor unit is lower than that of indoor unit H 1 30m Below Between each indoor unit H 2 15m Below Maximum Piping Length Between Each Multi ki...

Page 12: ...connected to the indoor unit be sure to use an optional parts of the multi kit pipe set in order to prevent the uneven distribution of the refrigerant and causing the unit s capacity reduction Do not connect using the connector 1 Line branch use the line branch pipe As shown below Main pipe The pipe between each multi kit pipe or the pipe between outdoor units to first multi kit pipe Main Branch T...

Page 13: ... Correct Setting Wrong Setting First Main Branch Second Main Branch First Branch Second Branch Third Branch First Main Branch Second Main Branch First Branch Second Branch Third Branch X Wrong Outdoor Outdoor Outdoor Outdoor First Main Branch First Main Branch Second Main Branch Second Main Branch First Branch First Branch Second Branch Second Branch Third Branch Third Branch X Wrong Fourth Branch...

Page 14: ...vibration of the piping Pay special attention in case of short piping length 4 Please perform the air tight test Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves Perform the air tight test Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit Do ...

Page 15: ...nt R410A which directly touch refrigerant 3 If vacuum degree of 0 1MPa 750mmHg is not available it is considered that leakage exists Check for any gas leakage once again If no leakage exists operate the vacuum pump for one to two hours 5 4 The Additional Refrigerant 1 Outdoor unit has been filled with refrigerant but still based on the length of pipe filled with an appropriate amount of refrigeran...

Page 16: ... will result in weight percent composition changes so can not directly add refrigerant treatment must be re processing system 5 6 Caution of Measure Pressure Data from The Check Joints Measure pressure data of work please from the check joints of gas line stop valve right figureⒶ and the check joints of piping line right figureⒷ to connect And then please according to the different operation state...

Page 17: ...Supply 3Φ 60Hz Maximum Current A ELB Earth Leakage Breaker Power Switch Power Supply Size mm2 Earth Wire Size mm2 Transmission Cable Size Number of Poles Rating Sensitivity Current mA Rating Current A Switch Capacity A Fuse Capacity A 1 2 2 3 4 5 RAM 200FPS 230V 22 3 30 30 60 30 3 5 5 5 2 Core Shielded Twist Pair Cable 0 75mm2 Total Length 1000m Below RAM 250FPS 29 40 40 5 5 RAM 270FPS 37 100 50 1...

Page 18: ...tion wiring construction The transmission cable of indoor and outdoor unit and the 220V power source cord be sure to keep the distance of more than 5 6cm Therefore do not use the coaxial cable If the transmission cable and power source cord connecting wrong will cause the PCB of the outdoor unit burning Please pay special attention 10 Indoor and outdoor unit s power source cord and connection wiri...

Page 19: ...gs shall be attached the insulation tape or insulation sleeve Χ Ο Fold the wire and reserve for a maintenance operation the desired length Prevent need to remove the wiring plug for maintenance Cord Band Operation 1 When wire through the cord band appropriately tighten it as show below 2 Make sure the cord with high and low pressure sensor isolation 3 Tighten the cord to be isolated with pipe comp...

Page 20: ...Do not input the power source to the terminal No 1 2 of transmission wiring 3 When power source wiring phase error the unit can not be operated and the remote controller display alarm code 05 At this time please refer to the electrical box caution nameplate check the phase of the first side and replace it The phase of the replacement work please process under the power source turn off 4 Does the o...

Page 21: ... operation 3 2 Depress RUN STOP switch The TEST RUN operation will be started The 2 hours OFF TIMER will be set and the TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again 3 3 To end the test run wait for 2 hours or push RUN STOP switch again Number of The Unit 0 1 2 3 4 10 11 63 Timer Setting Display Left Two Digit 01 02 03 04 05 11 12 64 Re...

Page 22: ...ity Low Pressure Thermistor Outdoor 31 System Incorrect Capacity Setting of Outdoor and Indoor Unit Incorrect Capacity Code Setting of Combination Excessive or Insufficient Indoor Unit Total Capacity Code outside of 80 120 35 Incorrect Setting of Indoor Unit No Duplication of Indoor Unit No In Same Ref Gr or The Connection Unit Number Exceeds The Maximum Number of Combination 38 Outdoor Unit Abnor...

Page 23: ...rigerant Temperature Operating Mode Cool Discharge Gas Temperature Td Liquid Pipe Temperature Te 8 Check Pressure Discharge Pressure Pd MPa Suction Pressure Ps MPa 9 Check Voltage Rated Voltage V Operating Voltage L1 L2 V L1 L3 V L2 L3 V Starting Voltage V Phase Imbalance 10 Check Compressor Input Running Current Input kW Running Current A A 11 Is the refrigerant charge adequate 12 Do the operatio...