Ð 142 Ð
MODEL RAM-70QH4
RAM-80QH4
◇
Expansion valves
¥ The expansion valves are initialized when power is supplied. The valve for unit 1 is fully closed (520
pulses), and then that for unit 2 is fully opened (480 pulses). When the valve for unit 1 is fully closed (0
pulse), start-up is possible.
¥ The start openings are held during the steady speed period when the compressor is started. After the
steady speed period is finished, the TD control is entered. The start openings are set to PSTARTH when
the outdoor temperature at start 40ûC or more, and to PSTART when it is less than 40ûC.
◇
Compressor rotation speed
¥ When the compressor is started, the SDRCT1 speed / TSTKTM1 second is held.
After the steady speed period is finished, the speed increases at the rate of SDSTEP speed / TSKSPT
second until the target speed is reached.
Power
Power
Unit1
Unit2
Unit1
Unit2
Heating output
Outdoor fan
Compressor
rotation speed
Operation
Rush-in
prevention
Turns on
for cooling
Turns on
for heating
Cooling output
Compressor
Reversing valve
Power
relay
Expansion
valve
520
480
520
480
0
0
Cooling
Cooling
approx. 100ms
TSKTM1-C
SDRCT1-C
PSTARTC2$
PSTARTC2$
100ms
1s
1s
1s
Start sequence
SDSTEP rpm /
TSKSPT sec.
31.25pps
「
Outdoor temperature
≧
40ûC
」
「
Outdoor temperature
≧
40ûC
」
CMAX2
Start enabled
Initialization finished
Hold
Hold
Hold 500ms
Hold 500ms
Hold
Hold
< TD c ÆN corr distribution control >
< TD c ÆN corr distribution control >
¥ See other sections for details of expansion valve TD control, ÆN correction and distribution control.
¥ TSKTM1, SDRCT1, SDSTEP, TSKSPT, CMAX2, PSTART and PSTARTH are EEPROM data.
¥ Unit 3 and 4 operation is the same as unit 1 and 2.
However, the outdoor unit fan is operated with the type A compressor.
¥ Wiht RAM-70QH4, type B compressor operates unit 3 only.
※
Summary of Contents for RAD25QH4
Page 3: ... 0Ω 112 3 4 1 5 6 7 7 8 9 4 DANGER ...
Page 10: ... SPECIFICATIONS EU1013DD 2 ...
Page 11: ... EU1013DD 2 ...
Page 31: ... 0 1 2 3 1 4 5 6 4 7 8 9 4 1 2 1 0 ...
Page 32: ... 1 2 3 4 1 2 5 6 2 5 6 7 2 28 2 9 9 1 1 2 7 6 8 2 8 ...
Page 33: ... 0 1 0 1 1 1 0 1 1 2 3 4 0 5 3 6 7 3 6 7 8 3 39 3 3 8 7 9 3 9 2 2 1 2 2 ...
Page 35: ... 0 1 2 3 2 456 7 0 1 8 9 5 5 8 3 8 5 3 4 4 8 8 3 8 3 3 7 A 3 3B C 9 8 D ...
Page 127: ... 0 1 22 3 3 4 567 89 5 8 8 3 567 89 ...
Page 152: ... 0 1 0 2 3 5 6 1 7 6 6 3 5 3 5 8 9 9 ...
Page 154: ... A 0 11 2 3 1 1 3 1 3 4 4 5 A 6 8 3 1 11 1 1 1 5 A 6 9 ...
Page 162: ... Mode Refroidissement 0 1 2 3 4 55 6 7 85 9 6 7 A 75 1 B B 6 A 75 1 B B C 9 ...
Page 183: ... 0 1 2 3 4 0 3 4 5 1 5 5 6 7 8 1 5 1 9 1 0 5 1 9 9 5 ...
Page 184: ... 01 0 2 3 4 3 0 5 3 3 0 3 0 067 8 3 0 7 3 0 3 9 3 9 1 9 1 0 A 0 B ...
Page 188: ... 0 2 2 3 4 567 3 4 567 3 4 567 3 4 567 8 9 2 8 9 2 4 6 0 0 6 0 4 ...
Page 194: ... 1 2 3 4 5 6 7 6 6 7 6 8 9 9 9 8 9 9 9 8 9 9 5 9 9 5 9 9 A A 2 3 4 9 9 ...
Page 203: ... 0 1 0 0 2 0 3 3 4 3 3 5 5 0 0 0 0 5 5 0 5 0 1 32 6 6 6 76 0 8 9 0 0 0 0 ...
Page 204: ... 0 1 2 3 4 5 6 2 2 3 7 7 1 3 7 2 2 8 7 1 2 29 9 5 6 2 3 2 2 2 29 9 5 9 0 3 7 2 2 4 0 0 3 6 ...
Page 207: ... 0 1 2 1 0 1 3 41 3 41 1 2 1 ...
Page 211: ... 0 1 23 4 1 03 4 1 4 1 5 6 4 7 8 7 7 8 7 7 8 7 7 8 7 5 0 9 0 9 5 5 5 5 5 5 5 5 5 5 ...
Page 212: ... 0 1 0 234 0 5 134 5 0 0 5 0 0 5 6 7 8 9 8 8 9 8 8 9 8 8 9 8 6 1 1 0 0 ...
Page 214: ... 7 Circuit de contr le facteur de puissance 0 ...
Page 217: ... 0 0 1 2 3 4 ...
Page 221: ... AT STARTING OPERATION 0 0 OTHERS 1 2 1 3 2 0 0 ...
Page 226: ... 0 0 1234 5 5 6 7 8 8 0 0 0 7 0 9 0 0 2 0 50 0 0 0 0 0 0 9 0 0 0 0 0 0 0 5 0 0 0 0 0 0 ...
Page 228: ... FIXATION 0 1 2 3 1 40 0 1 2 3 1 1 6 2 3 1 22 7 8 9 2 3 1 6 8 2 40 0 2 3 1 0 0 6 ...
Page 230: ... 01234 54 567 8 94 4 4 8 8 2 8 8 7 FIXATION FIXATION ...
Page 232: ... 0 1 2 3 4 1 1 6 7 8 7 7 9 8 0 3 4 8 FIXATION 3 1 3 1 ...
Page 236: ... FIXATION 0 1 2 2 3 4 5 6 ...
Page 249: ... 0 1 1 234 354 64 234 354 74 8 2349 354 4 49 64 49 64 239 354 74 7 1 ...
Page 280: ...Ð 307 Ð MODEL RAD 25QH4 RAD 40QH4 MODELE 67 11 ...
Page 293: ...TC NO 0757EF RAF 25NH4 RAF 50NH4 RAD 25QH4 RAD 40QH4 RAM 70QH4 RAM 80QH4 ...