– 70 –
1/ 2/ IPM (Intelligent Power Module)
3/ Service Switch
4/ Self-Diagnosis Lamp
Remove the compressor connector.
If your first attempt
fails, wait 3 minutes
(for the unit to re-
start) and check the
self-diagnosis lamp
status again.
Check outdoor electrical parts.
Check the refrigerating
cycle.
Normal
No
Yes
Check the drive
circuit (IPM) using
the PRD checker.
Check the position
sensor circuit.
With the unit set in the operating
state, press the start/stop
button.
Does the unit operate for
approximately 2 seconds (the
LD303 coming on) and then
stop due to a failure of switching
(the lamp blinking 4 times)?
OUTDOOR UNIT
LD303
LD302
LD301
MAIN P.W.B.
SERVICE SWITCH
HIC
IPM
Summary of Contents for RAC-E08H2
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E08H2A RAS E10H2A INDOOR UNIT Unit mm ...
Page 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC E08H2 RAC E10H2 OUTDOOR UNIT ...
Page 22: ... 20 CIRCUIT DIAGRAM MODEL RAS E08H2A RAS E10H2A ...
Page 23: ... 21 RAC E08H2 RAC E10H2 MODEL ...
Page 25: ... 23 ...
Page 27: ... 25 ...
Page 28: ... 26 ...
Page 30: ... 28 ...
Page 31: ... 29 ...
Page 47: ... 45 ...
Page 48: ... 46 ...
Page 50: ... 48 ...
Page 51: ... 49 ...
Page 52: ... 50 ...
Page 54: ... 52 ...
Page 77: ... 75 ...
Page 81: ... 79 ...
Page 82: ... 80 ...
Page 83: ... 81 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E08H2A RAS E10H2A ...
Page 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA ...
Page 95: ...HITACHI RAS E08H2A RAC E08H2 RAS E10H2A RAC E10H2 SM0026 ...