– 59 –
< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
DC Fan Motor has broken invites 1A Fuse burned. Please replace both DC Fan Motor and 1A Fuse
together.
It will makes “Fan Lock Stop” when something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make “Fan Lock Stop” by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case
unit will be restart again after a while.
In case of “ Fan Lock Stop” even though the DC Fan Motor is rotating correctly, the possible cause in Fan
Motor problem or control board problem. Stop after the Fan motor runs 2 minutes, Fan Motor may be
broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor directly due to the built in control circuit in Fan Motor.
Summary of Contents for RAC-E08H2
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E08H2A RAS E10H2A INDOOR UNIT Unit mm ...
Page 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC E08H2 RAC E10H2 OUTDOOR UNIT ...
Page 22: ... 20 CIRCUIT DIAGRAM MODEL RAS E08H2A RAS E10H2A ...
Page 23: ... 21 RAC E08H2 RAC E10H2 MODEL ...
Page 25: ... 23 ...
Page 27: ... 25 ...
Page 28: ... 26 ...
Page 30: ... 28 ...
Page 31: ... 29 ...
Page 47: ... 45 ...
Page 48: ... 46 ...
Page 50: ... 48 ...
Page 51: ... 49 ...
Page 52: ... 50 ...
Page 54: ... 52 ...
Page 77: ... 75 ...
Page 81: ... 79 ...
Page 82: ... 80 ...
Page 83: ... 81 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E08H2A RAS E10H2A ...
Page 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA ...
Page 95: ...HITACHI RAS E08H2A RAC E08H2 RAS E10H2A RAC E10H2 SM0026 ...