– 68 –
No.
Blinking of Timer lamp
Reason for indication
Possible cause
Reversing valve defective
When the indoor heat exchanger
temperature is too low in the
heating mode or it is too high in the
cooling mode.
Outdoor unit is under forced
operation
Outdoor unit electrical components
defetive
When the outdoor unit is in forced
operation or balancing operation
after forced operation
Indoor/outdoor interface defective
When the interface signal from the
outdoor
When the same error mode is detected
8 times within 30 minutes from outdoor
unit electrical components.
(However, when error is detected 8
times within two hours only for outdoor
thermistor.)
unit is interrupted.
Room thermistor or heat exchanger
thermistor is faulty
When room thermistor or heat
exchanger thermistor is opened
circuit or short circuit.
Over-current detection at the DC fan
motor
when over-current is detected at the
DC fan motor of the indoor unit.
IC401 or IC402 data reading error
When data read from IC401 or
IC402 is incorrect.
(1) Reversing valve defective
(2) Heat exchanger thermistor
disconnected
(only in the heating mode)
(Note)
The malfunction mode is entered the
3rd time this abnormal indication
appears (read every 3 minutes).
Electrical parts in the outdoor unit
(1) Indoor interface circuit
(2) Outdoor
Outdoor unit electrical components
(For details, operate again using
remote comtroller and check from
self-diagnosis display of outdoor
unit.)
interface circuit
(1) Room thermistor
(2) Heat exchanger thermistor
(1) Indoor fan locked
(2) Indoor fan motor
IC401 or IC402 abnormal
1
2
3
4
5
6
7
(
Lights for 0.35 sec. at interval of 0.35 sec.)
10 times
3 times
1 time
2 times
13 times
2 sec.
2 sec.
2 sec.
2 sec.
2 sec.
1
9 times
2 sec.
(3) Indoor control P.W.B.
4 times
2 sec.
<Cautions>
(1)
If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2)
If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit.
(3)
To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Model RAS-E08H2A, RAS-E10H2A
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301
blink.
SELF-DIAGNOSIS LIGHTING MODE
Model: RAS-E08H2A, RAS-E10H2A
Summary of Contents for RAC-E08H2
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E08H2A RAS E10H2A INDOOR UNIT Unit mm ...
Page 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC E08H2 RAC E10H2 OUTDOOR UNIT ...
Page 22: ... 20 CIRCUIT DIAGRAM MODEL RAS E08H2A RAS E10H2A ...
Page 23: ... 21 RAC E08H2 RAC E10H2 MODEL ...
Page 25: ... 23 ...
Page 27: ... 25 ...
Page 28: ... 26 ...
Page 30: ... 28 ...
Page 31: ... 29 ...
Page 47: ... 45 ...
Page 48: ... 46 ...
Page 50: ... 48 ...
Page 51: ... 49 ...
Page 52: ... 50 ...
Page 54: ... 52 ...
Page 77: ... 75 ...
Page 81: ... 79 ...
Page 82: ... 80 ...
Page 83: ... 81 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E08H2A RAS E10H2A ...
Page 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA ...
Page 95: ...HITACHI RAS E08H2A RAC E08H2 RAS E10H2A RAC E10H2 SM0026 ...