background image

2

6

1

3

4

5

INDOOR UNIT

32mm

Removing

Attaching

3

Installation of Drain Hose

 1 

 2 

 5 

 6 

 3 

 4 

 8 

20mm

Outdoor

790mm

398mm

390mm

200mm

200mm

24mm

26mm

297mm

130mm

130mm

304mm

210mm

530mm

48mm

45mm

52.5mm

113mm

113mm

16mm

52mm

60mm

ø80mm

80mm

450mm

ø80

60mm

50mm

3

Cut the heat insulation sheet refrigerating pipe aligning to the

7

insulation sheet of the pipe and fix them temporarily with

tape.

4

Wrap the refrigerating pipe and two way air exchange hose
with 

7

insulation sheet and fix it with tape. Tape must not be

overtightened. (Refer to “Heat insulation and finish of the
piping” on Page 11.)

Place the tip of air duct for horizontally backward piping in the
direction shown in the drawing on the right.

5

Wrap two ways air exchange hose with  

7

insulation sheet

until wall hole.

6

Form the refrigerating pipe according to the wall hole position.
Especially in case of horizontally backward piping, follow the
instruction below to carry out accurate forming.

<Forming of refrigerating pipe for horizontally backward piping>
(1) Referring to the drawing on the right, start bending the

refrigerating piping within wall hole range.

(2) When forming, bend the refrigerating pipe with the smallest

radius as shown the drawing on the right. (Finishing will be
better if the center of the forming is moved a little to the
right.)

• Procedures to fix the 

4

 remote controller mounting screw.

1

 PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

Preparation

Changed of Drain Hose and Installation Procedures

• Exchange the location of drain hose and drain cap while installing

the pipe from the left side as shown in below. Be sure to plug in
the drain hose until the insulating material folds upon itself.

Part Name

%

 ø25 Two way air

^

 ø20 Two way air

@

 Air duct for piping

=

 Net

~

 Hood

#

 Joint

$

 Elbow

exchange Hose (A)

exchange Hose (B)

connection from left

Backward piping

(

 ● 

)

Remark

2

 PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

Preparation of Refrigerating Pipe and Two Way Air Exchange Hose

In case of backward piping

1

Form the refrigerating pipe within the wall hole range.

INDOOR UNIT / OUTDOOR UNIT

HITACHI SPLIT UNIT AIR CONDITIONER

INSTALLATION MANUAL

FOR SERVICE PERSONNEL ONLY

SAFETY PRECAUTION

• Carefully read through the procedures of proper installation

before starting installation work.

• The sales agent should inform customers regarding the correct

operation of installation.

Tools Needed For Installation Work

(Mark       is exclusive use tool for R410A)  •  

ª·

 Screwdriver

• Measuring Tape • Knife • Saw • ø65mm Power Drill
• Hexagonal Wrench Key (      4mm) • Wrench (14,17,19,
22mm)     Gas leakage Detector • Pipe Cutter • Putty
• Vinyl Tape • Pliers  • Flare Tool       Vacuum Pump Adapter
     Manifold Valve       Charge Hose       Vacuum Pump

• Read the safety precautions carefully before operating the unit.
• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING ............. Incorrect methods of installation may cause death or serious injury.
CAUTION .............. Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit
as described in the user’s guide. Ask customers to keep this installation manual together with the instruction manual.

 WARNING

• Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work

yourself.

• Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric

shock and fire.

• Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose

danger.

• Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work.

Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and fire may occur due to the use of low quality
wire or improper work.

• Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the

wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and
loose contact may cause over-heating and fire.

• Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or stronger vibration

may occur.

• Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

• When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A) does not enter the

refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

• Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

• After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into

contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

• Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repairs may result in water leakage, electric shock and fire, etc.

• Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not

connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause
electric shocks.

• When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while

the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing an
explosion or injury.

• When installing the unit, be sure to install the refrigerant pipe before starting the compressor.

If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the
refrigeration cycle may increase abnormally which could result in a rupture and injury.

 CAUTION

• A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other

installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.

• Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks

around it.

• Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your furniture.

• An IEC approved power cord should be used. Power cord type: NYM.

INDOOR UNIT

THE CHOICE OF MOUNTING SITE

  (Please note the following matters and obtain permission from customer before installation.)

 WARNING

• The unit should be mounted at stable, non-vibratory location which

can provide full support to the unit.

 CAUTION

• No nearby heat source and no obstruction near the air outlet is

allowed.

• The clearance distances from top, right and left are specified in

figure below.

• The location must be convenient for water drainage and pipe

connection with the Outdoor unit.

• To avoid interference from noise, please place the unit and its

remote controller at least 1m from the radio and television.

• To avoid any error in signal transmission from the remote controller,

please put the controller far away from high-frequency machines
and high-power wireless systems.

OUTDOOR UNIT

 WARNING

• The Outdoor unit must be mounted at a location which can support heavy

weight. Otherwise, noise and vibration will increase.

 CAUTION

• Do not expose the unit under direct sunshine or rain. Besides, ventilation

must be good and clear of obstruction.

• The air blown out of the unit should not point directly to animals or plants.
• The clearances of the unit from top, left, right and front are specified in

figure below. At least two of the above sides must be open air.

• The installation height should be at least 2,300 mm or more from the

floor.

• Be sure that the hot air blown out of the unit and noise do not disturb the

neighbourhood.

• Do not install at a location where there is flammable gas, steam, oil and

smoke.

• The location must be convenient for water drainage.
• Place the Outdoor unit and its connecting cord at least 1 m away from the

antenna or signal line of television, radio or telephone. This is to avoid
noise interference.

Figure showing the Installation of Indoor and Outdoor Unit.

No.

Item

Qty

%

Two Way Air Exchange

1

Hose (A)

(ø25 

×

 2000)

^

Two Way Air Exchange

1

Hose (B)

(ø20 

×

 700)

&

Cushion

1

No.

Item

Qty

1

Hanger

1

2

Screw for Hanger

5

(4.1 

×

 32)

3

AAA size Battery

2

4

Remote Controller

1

Mounting Screw

(3.5 

×

 15)

5

Holder

1

6

Remote

1

Controller

7

Insulation Sheet

3

8

Bush

1

9

Drain Pipe

1

0

Switch Cover

1

-

Purifying Filter

1

=

Net

1

~

Hood

1

!

Nano-Titanium

1

Deodorizing/Dust
Collecting Fresh
Air In Filter

@

Air Duct for Piping

1

Connection from left

#

Joint

1

$

Elbow

1

The components of 

8

 & 

9

 are included

in the package of the outdoor unit.

The Length of Indoor Unit

Connecting Cord

above 0.9m

above 1.6m

330

310

(10)

10

500

35

50

12

125

Dimension of Mounting Stand of

the Outdoor Unit

(unit : mm)

Mounting Stand

Direction of Piping

Backward piping
from left

Connection

There are 6 directions allowed, namely, backward
piping, backward piping from left, horizontally
piping from right, horizontally piping from left,
vertically down from right, vertically down from
left.

• The refrigerating machine oil is

easily affected by moisture. Use
caution to prevent water from
entering the cycle.

• The difference in height between

the indoor and outdoor unit should
be kept below 10m.

• The connecting pipe, no matter big

or small, should all be insulated with
insulation pipe and then wrapped
with vinyl tape. (The insulator will
deteriorate if it is not wrapped with
tape).

The connection of insulated drain
hose.

Inner diameter ø16mm

Please use insulated drain hose for
the indoor piping (commercial
product).

Be sure to com-
pletely seal any
gap with putty.

above 200mm

 above 50mm

 give clearance as
wide as possible

maxim

um pipe length 20m

abo

ve 300mm

must not bend

above 50mm

above 50mm

above 50mm

2,300 mm or more

Used in horizontal piping

abo

ve 0.45m

The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator
is insufficient, please use
commercial products).

(

)

 above 300mm

above 100mm

above 200mm

above 50 mm when
installed on the
ceiling of balcony

1

Installation of Wall Penetration and Installation of Protection Pipe

 CAUTION

• The draining of the water container inside the Indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted

towards the side of drain hose. Otherwise, condensed water may overflow the water container.

Direct Mounting on the Wall

• Please use hidden beams in the wall to hold the hanger.

Visible outline of the
indoor unit

Drain hose

Wall hole

Drain hose

Wall hole

Screw the hanger at the positions possibly near the upper and lower hooks
where the indoor unit is hung. Use 4 or more screws to fix the hanger.

Wall

1

 Hanger

2

 Screw for  hanger

ø4.8mm

Wall

ø4.4mm

Wall

above 50 mm

Ceiling

4.1 

×

 32

screws

Plug (Procure locally)

4

 Remote controller

mounting Screw

Plug (Procure locally)

1

Two Way Air Exchange Hose Installation

The two way air exchange function is included in this model. Please follow the “two way air exchange hose” installation
instructions when mounting.

Conditions when the two way air exchange should not be operated 

(Please install only with the customer’s consent)

.

• The two way air exchange should not be operated under the following conditions:

(A) When the two way air exchange hose cannot be vented directly outside the room (mounting work specified for the embedded ducting).
(B) When there is a source of a questionable odor, smoke, or oily smoke in the vicinity of the opening of the two way air exchange hose, even if the

mounting work directly vents the two way air exchange hose outside the room.

• The fresh air in should not be operated (only exhaust can be operated) under the following conditions:

(C) When there is space to vent the two way air exchange hose between the internal and external walls, which leads outside the room, even if the

mounting work cannot directly vent the Two way air exchange hose outside the room (conventional construction methods).

• Please set the Two Way Air Exchange Selection Switch according to the mounting configuration (refer to “Setting the Two Way Air Exchange Selection

Switch on page 12).

In the case of (A) or (C) in the above, two way air exchange can be operated if the two way air exchange hose is vented outside the room through a hole
in the wall (refer to “End Treatment of Two Way Air Exchange Hose” on page 15).

[Dimensions when Installing included Fittings]

Within 1.4m

Within 1.4m

Within 1.4m

Within 1.4m

Dimensions when installing the fitting for ø25 two way air exchange hose (When piping
connection is left, ø20 hose shall be attached first. The details shall conform to the
table.)

UNUSED ACCESSORY

Unused accessories may become necessary in case of transfer of air conditioner. Request your customer to keep all the unused accessories together
with this installation manual and instruction manual.

Use of Accessories

Select (

) depending on the installation condition.

Vertically down from right
Horizontally piping from right

Backward piping from left
Vertically down from left

Horizontally piping from left

First attach 

^

 ø20 hose add

#

joint or 

$

 elbow, then use

this hose.

First attach 

^

 ø20 hose add

#

joint, then use this hose.

When Air Exchanger
cover (HC-DS5) is not
using.

Diagram Summarizing the Vertically Down from Left

Connecting cable

Refrigerating pipe

Two way air exchange hose

Drain hose

Diagram Summarizing the Horizontally Piping from Right

Two way air exchange hose

Refrigerating pipe

Drain hose

Diagram Summarizing the Horizontally Piping from Left

Two way air exchange hose

Refrigerating pipe

Drain hose

Connecting cable

Diagram Summarizing the Backward Piping from Left

Two way air exchange hose

Refrigerating pipe

Drain hose

Connecting cable

5

Heat Insulation Tape of the Two Way Air Exchange Hose

• Cover the parts of the two way air exchange hose which passes through the room with 

7

insulation sheet for hoses and wrap with tape to ensure there are no

spaces.

Two way air exchange hose

7

 Insulation sheet

 CAUTION

Ensure that the two way air exchange hose which
passes through the room is covered with insulation
sheet for hoses.

Dew may form on the two way air exchange hose and there
may be a possibility of water droplets forming.

7

 Insulation sheet

Perforated line

260mm

4

Installation of Air Duct for Piping Connection from Left

Only horizontally piping, except for the case where refrigerating pipe is connected after the indoor unit is hung on the wall.

• Cut the 

^

 two way air exchange hose (B).

• Wrap with insulation sheet and fix with tape so that there is no gap between

insulation sheet wrapped and insulation sheet of 

@

 air duct for piping

connection from left.

Cut

Wrap with tape

Insulation sheet of 

@

 air duct

for piping connection from left.

Wrap with tape

7

 Insulation sheet

3

Connecting and Fixing the Two Way Air Exchange Hose

In the case of ø25

Insulation sheet

In the case of ø20

• Please insert two way air exchange hose until the end of the outlet.

Insulation sheet

Bottom of two way air

exchange outlet

Cuff

2

Length Adjustment of the Two Way Air Exchange Hose

This model is supplied with two hoses. Details shall conform to the table in page 3.

Please ensure that the entire length of the two way air exchange hose is within 3m.

Please adjust the length of the two way air exchange hose by joining or cutting hoses, as deemed necessary.

Please shorten the length of the hose as much as possible to prevent the degradation of the two way air exchange operating performance.

=

Distance between the centre of the hole
in the wall from the opening of the two
way air exchange unit

Thickness
of the wall

Over 230mm

This will change according to the
installation outside the room

Target hose length

+

+

Procedures of Installation and Precautions

• Procedures to fix the hanger.
1. Drill hole on wall. (As shown in figure

below)

2. Push plug into the holes. (As shown in

figure below)

3. Fix the hanger on wall with 4.1 

×

 32

screw. (As shown in figure below)

1. Drill hole on wall. (As shown in figure

below)

Wall Penetration and Installation of Protection Pipe

• Drill a ø65~80mm hole on wall which is slightly tilted towards

the outdoor side. Drill the wall at a small angle. (ø70mm or more
is recommended)

• Cut the protection pipe according to the wall thickness.
• Empty gap in the sleeve of protection pipe should be completely

sealed with putty to avoid dripping of rain water into the room.

• Please ensure smooth flow of water when installing the drain

hose. Improper installing may wet your furniture.

• An IEC approved power cord should be used. Power cord type:

NYM.

 WARNING

Be sure that the wire is not in contact
with any metal in the wall. Please use
the protection pipe as wire passing
through the hollow part of the wall so
as to prevent the possibility of
damaged by mouse.
Unless it seals completely any air with
high humidity flows from outdoor and
any dew may drop.

WALL

Protection
pipe

Seal with
putty

Seal with
putty

Sleeve of
protection pipe

2-5mm

Indoor

2

Installation of the Indoor Unit

2. Push plug into the hole. (As shown in

figure below)

Preparation of Installation

Remove the Front Panel

• To remove front panel, please refer to page 13 “Removing and Attaching

the Front Panel”.

• Make sure to use both hands to attach and remove the front panel.

Remove the Top Grill

• To remove top grill, please refer to page 14 “Attaching the Top Grill”.

Remove the Low Cover

• Pull at the 

1

 and 

2

 in the directions as shown by arrows to remove the

low cover.

• To attach the lower cover, attach 

2

 first and then attach 

1

 by rotating it

around the 

2

 as the fulcrum.

Cutting Low Cover Bush

• While installing the pipe from the right, left or

bottom side, use a knife to cut openings as
shown in figure. Then smoothen the edges of
openings with a file.

Openings

Openings

• Please use pliers to

pull out the drain cap.
(This is an easier way
to remove the drain
cap).

 CAUTION

• Be sure to insert drain

hose and drain cap firmly.
Insufficient insert may
result in water leakage.

• Push the pipe deeply until

the insulating section of
the drain hose end gets
over the rib at the indoor
unit side.

Drain cap

Drain hose

Drain cap

• Remove low cover.
• Insert drain cap up to

the location securely till
the cap stops.

Drain hose

 CAUTION

• The rubber strap used for fixing the insulator should not be

tied with great force. Otherwise, this will damage heat insulation
and causes water condensation.

• Please pull the lower part of the Indoor unit outwards to check

if the unit is hooked onto the hanger. Improper installation may
cause vibration and noise.

• Transform the piping while holding down the lower portion of

pipe-support by hand.

Pipe

Rubber strap tied with
great force.

Transform after
bending downward.

Pipe support

 CAUTION

Be sure that the drain hose is not loosely connected bend or proper
condition like left figure.

• Pull up the [PULL] sections at the bottom of the indoor unit and pull the bottom plate towards you. Then the claws

are released from the mounting plate. (The [PULL] sections are indicated by 2 arrows in the right figure.)

[PULL] mark positions

How to Remove Indoor Unit

Bending
upwards

Condensed
water pond

Ditch

Condensed water pond

Bottom of two way air

exchange outlet

 CAUTION

Ensure to use air duct insulation when connecting two
way air exchange hose by horizontally piping from left.

Otherwise, dew may form and odor, moss etc may form.

Perforated line side

If the starting point of
refrigerating pipe
bending is projected
from the wall hole range
or if the bending radius
is too large, the indoor
unit may be lifted from
wall and this may cause
poor finishing.

Refrigerating pipe

Join the refrigerating pipe, drain
hose, two way air exchange hose
and connecting cord, and then fix
them temporarily with tape.

Two way air exchange hose

Drain hose

Wrap with tape

2

Connect the two way air exchange hose. (Refer to page 4 “Connecting
and Fixing the Two Way Air Exchange Hose.”)

3

Referring to the drawing below, join the refrigerating pipe, drain hose,
two way air exchange hose and connecting cord, and then fix them
temporarily with tape.

4

Wrap the through-hole portion with tape.
• If the existing wall hole is deviated from the pipe position,

cover the two way air exchange hose located at the back of
the indoor unit with heat insulation sheet, with the joint of
insulation sheet facing up.

 7 

INSTALLATION  AFTER CONNECTION OF REFRIGERATING PIPES 

(Horizontally backward piping)

1

Connect the two way air exchange
hose. (Refer to page 4 “Connecting
and Fixing the Two Way Air Exchange
Hose”.)

2

Form the two way air exchange hose
and connecting cord as shown in the
drawing.

Refrigerating pipe

Two way air
exchange hose

Cut

Wrap with tape

@

Air duct for piping
connection from left

7

Insulation sheet

Refrigerating pipe
insulation sheet

Refrigerating pipe
insulation sheet

Point the tip downward
to the inner of indoor
unit.

@

Air duct for piping
connection from left

@

Air duct for piping
connection from left

Two way air
exchange hose

Refrigerating pipe

Projection

Hook

about 15cm

Temporary
stand

1.15m

The end of the refrigerating pipes are at locations
marked with “

” symbol.

below 5mm

Wall hole for two way air exchange hose
(  more than ø40mm)

Insert polyester core (commercial product) into the pipe.

Please bend at a small radius
to form an arc.

Please bend at a small
radius to form an arc.

Place the star ting point of
refrigerating pipe bending within
the wall hole range.

Wall hole
range

In this case of horizontally piping and downward piping from right

1

Carry out refrigerating pipe forming.

2

Temporary join the refrigerating pipe, drain hose, two way air exchange hose
and connecting cord with tape.

Drain hose

Two way air exchange hose

Refrigerating pipe

Layout of Horizontally piping from right.

Bottom cover
bush hole

 WARNING

Two way air exchange hose should be formed at
higher level than Part A to avoid trapping, etc.

If two way air exchange hose is formed at lower level
than Part A and trapping is caused, dew condensation
around the heat insulation sheet may drip onto electrical
parts and it may cause electrical shock or fire.

If the starting point of
refrigerating pipe
bending is projected
from the wall hole range
or if the bending radius
is too large, the indoor
unit may be lifted from
wall and this may cause
poor finishing.

@

Air duct for piping connection from left

7

Insulation sheet

5

Holder

Wrap with tape

Installation

1

Insert the pipe through the wall hole.

2

The upper part of the Indoor unit is hung on
the hanger.

3

The projection at the lower part of the Indoor
unit is hooked onto the hanger.

1

 Hanger

Refrigerating pipe

Connecting cord

Drain hose

Protection pipe

1

 Hanger

Projection

Lift the body of
the unit upwards
and then force it
downwards.

Two way air exchange hose

Please use 

#

 joint or  

$

elbow then connect 

%

 ø25 two

way air exchange hose (A).

Place the starting point of
refrigerating pipe bending within
the wall hole range.

7

Form the connecting cord and refrigerating pipe and put them
in the space on the lower side of the rear surface of the indoor
unit. Fix them with the holder.

8

Join refrigerating pipe, two way air exchange hose, connecting
cord and drain hose temporarily with tape and wrap the
through-hole portion with tape.

9

Attach the 

&

 cushion as shown in the drawing.

If refrigerating pipe is connected at the back of the
indoor unit, make the wall hole for two way air exchange
hose on the right

• Insert refrigerating pipes and connecting cord through the wall hole.

THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT

• The refrigerating pipe should be adjusted to fit into the hole on the wall and then ready for further connection.
• The terminals of 2 connected pipes must be covered with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
• Connect the connecting cord after removing low cover. (Refer to "CONNECTION OF POWER CORD" on page 10.)
• After adjustment, fit the connecting cord and pipes into the space available under the unit. Use holder to hold them tight.
• Holder can be attached at the either of 2 places. Please select the easier position.

1

Connect two way air exchange hose. (Refer to “Connecting and Fixing the Two Way Air Exchange Hose” on
Page 4.)

2

Hang the indoor unit on the hanger.

3

Place the temporary stand under the right rear surface of the indoor unit to lift the lower side of the unit by
approximately 15cm.

4

Connect the refrigerating pipe. (Refer to “Pipe connection” on Page 9)

5

Wrap the pipe connection with tape so that there is no gap between heat insulation sheet. (Refer to “Heat
Insulation and Finish of the pipe” on page 11.)

6

Insert the drain hose and two way air exchange hose into the wall hole. (At this time, pull out the two way air exchange hose from the hole on the
right.) Especially in case of horizontally backward piping, insert the hose following the explanation below.

7

Connect the connecting cord. (Refer to “Connection of Power Cord” on
Page 10).

8

Form connecting cord and refrigerating pipe and put them in the space on
the lower side of the rear surface of the indoor unit. Fix them with the holder.

9

Remove the temporary stand under the indoor unit and fit the lower part of
the indoor unit in the fixing tab on the hanger.

Protection pipe

5

Holder

Connected
section

Drain
hose

Heat insulation
pipe

Connecting cord

Pull this to the front
during the connec-
tion of refrigerating
pipe to ease task.

7

Insulation sheet

Two way air exchange hose

Connecting cord

Refrigerating
pipe

 CAUTION

• Do not over tighten vinyl tape on pipe heat insulation

sheet. Do not over tighten to avoid loss of heat
insulating effect and dew condensation.

• Pull the lower part of the indoor unit towards you

and confirm that the tab of the indoor unit is fit in
the installation plate. If the tab is not fitted in securely,
vibration of the indoor unit becomes larger.

OUTDOOR UNIT

• Please mount the Outdoor unit on stable ground to prevent vibration

and increase of noise level.

• Decide the location for piping after sorting out the different types of

pipe available.

• When removing side cover, please pull the handle after undoing

the hook by pulling it downward. Reinstall the side cover in reverse
order of the removal.

Condensed Water Disposal of Outdoor Unit

• There is holes on the base of Outdoor unit for condensed water to

exhaust.

• In order to flow condensed water to the drain, the unit is installed on

a stand or a block so that the unit is 100mm above the ground as
shown figure. Join the drain pipe to one hole.

Pull downward

Please face this side (suction
side) of the unit to the wall.

Please remove side cover when
connecting the piping and
connecting cord.

Push

• Cover the drain hole with a bush. To install the bush, put it on the

drain hole as shown in the figure and press the both sides of the
bush to fit into the hole. After installation, check whether the drain
pipe and bush cling to the base firmly.

• Install the outdoor unit horizontally and make sure that condensate

drains away.

In case of using in chilly area

Especially, in case that there are many snows by very cold in chilly
area, condensed water freezes on the base and may result not to
drain.  In this case, please remove the bush and the drain pipe at the
bottom of unit. (Left and centre near discharge portion of air, each
1 place). It becomes smooth drain. Ensure that the distance from the
drain hole to the ground is 250 mm or more.

Drain hole

9

 Drain pipe

Outer diameter:
16mm  or more

Above 100mm

Base

Drain hole

8

 Bush

Push

8

 Bush

 CAUTION

Ensure to incline the two way air exchange hose and install from the top towards downward.

Dew may form on the two way air exchange hose and there may be a possibility of water droplets
forming.

• Insert the air duct for piping connection from left (13mm) into the cut-off

part of the two way air exchange hose (B), then wrap the connection with
tape.

Insert 13mm then
wrap with tape.

Insert 13mm then
wrap with tape.

@

 Air duct for piping

connection from left

&

Cushion

Attach at the edge of
R as guideline.

Attach above the mark.

You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth flow of condensed
water of the Indoor unit during installation. (Careless may result in water leakage.)

 CAUTION

Connecting cord

Bottom cover

Cord band screw

Cord band

Wall hole of ø80  is recommended.
The gap between the indoor unit and wall
surface may be big depending on the pipe
forming.

Cable drawer (right side)

When the power is supplied
from the indoor unit, pull the
power cable from the cable
drawer at the right or left
side of the indoor unit.

This mark shows the
center line of wall hole.

This mark shows the
center line of wall hole.

A

Wiring Connection

• Refer to page 10.

Refrigerating pipe

52mm

Connecting Cord

This mark shows the
center line of wall hole

0~10

ø80

Two way air exchange hose

Drain hose

Connecting cord

Refrigerating pipe

Refrigerating pipe

Wall hole

390mm

Level

1

 Hanger

Pipe hole

Weight

Line

2

Screw for Hanger

ø80

52mm

(ø65)

ø80

Wall hole of
Refrigerating pipe

Connecting cord

Wall hole
(more than ø40)

Drain hose

Two way air
exchange hose

RAS-D10EX2_A1_EN

12/13/05, 11:41 AM

1

  RAS-D10EX5 / RAC-D10EX5
  RAS-D14EX5 / RAC-D14EX5

< EE0003443-IM > 

Summary of Contents for RAC-D10EX5

Page 1: ... way air exchange hose 7 Insulation sheet CAUTION Ensure that the two way air exchange hose which passes through the room is covered with insulation sheet for hoses Dew may form on the two way air exchange hose and there may be a possibility of water droplets forming 7 Insulation sheet Perforated line 260mm 4 Installation of Air Duct for Piping Connection from Left Only horizontally piping except ...

Page 2: ...mp in the room where the indoor unit is installed and check the remote controller for normal operation Force cooling Operation When the service switch of the outdoor unit is pressed for 1 or more seconds the force cooling operation starts Use this mode when performing the failure diagnosis or collecting refrigerant into the outdoor unit Screw Cover Service switch If the switch is pressed for more ...

Page 3: ...almando manguera según sea necesario Reduzca al máximo la longitud de la manguera para evitar el empeoramiento de la función de intercambio de aire de dos sentidos Distancia entre el centro del agujero de la pared desde la abertura de la unidad de intercambio de aire de dos sentidos Grosor de la pared Más 230 mm Esta medida cambiará según la instalación exterior Longitud de la manguera Procedimien...

Page 4: ...este modo para realizar el diagnóstico de fallos o recoger refrigerante en la unidad interior Tornillo Cubierta Interruptor general si se presiona el interruptor durante uno o más segundos se pone en marcha el funcionamiento de refrigeración forzada si lo presiona uno o más segundos adicionales se detiene Extracción y Colocación del Panel Frontal Después de abrir el panel frontal completamente con...

Page 5: ...erire le spine nei fori come mostrato nella figura sottostante 3 Fissare il sospensore almuro mediante viti da 4 1x32 come mostrato nella figura sottostante 1 Praticare dei fori nel muro come mostrato nella figura sottostante Foratura del muro e installazione del tubo di protezione Fare un foro sul muro di ø65 80mm leggermente inclinato verso fuori Forare il muro con una leggera inclinazione ø70 o...

Page 6: ... il cavo sia collegato correttamente Accendere la lampada nella stanza in cui è installata l unità interna e controllare che il telecomando funzioni correttamente Operazione di raffreddamento forzato Quando l interruttore di servizio dell unità esterna viene premuto per almeno 1 secondo ha inizio l operazione di raffreddamento forzato Utilizzare questa modalità per eseguire la diagnosi degli error...

Page 7: ... Ô 52mm 390mm ÏÊ È 1 Ï ÛÈÔ Ó ÚÙËÛË ΔÚ ÛÙÔÓ ÙÔ Ô μ Ú È Ú ÌÌ 2 μ ÁÈ Ï ÛÈÔ Ó ÚÙËÛË ø80 52mm ø65 ø80 Óˆ fi 50mm Óˆ fi 50mm ÂÚ ÁˆÁfi ÁÈ Û Ó ÂÛË ÛˆÏ ÓˆÓ fi ÚÈÛÙÂÚ ø20 ÛÙÈ Ô ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú B ÛÙÈ Ô ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ÛÙÈ Ô ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ÛÙÈ Ô ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ΔÔ Ô Δ ÈÎ ÁÔÚ ÊÚ Á ÛÙ Ì ÛÙfiÎÔ ÔÛfiÙËÙ ÏÂÈÙÔ ÚÁ ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ÂÚÈÏ Ì ÓÂÙ È Û Ùfi ÙÔ ÌÔÓÙ ÏÔ Ú Î ÏÔ Ì ÎÔÏÔ ı ÛÙ ÙÈ Ô ËÁ  ÂÁÎ Ù ÛÙ ÛË Ï ÛÙÈ ...

Page 8: ...Ô Ê ÏÙÚÔ ÂÓ ÂÙ È Ó ÚÔÎ Ï ÛÂÈ ÌË Ê ÛÈÔÏÔÁÈÎÔ ıÔÚ Ô º ÏÙÚÔ Î ı ÚÈÛÌÔ Ú Û Ì ÂÚÈÏ Ì ÓÂÙ È Ï ÛÈÔ ÙÔ Ê ÏÙÚÔ Ó ÛÙ ÙÔ Ï ÛÈÔ ÙÔ Ê ÏÙÚÔ Î È ÛÙÔ fÊ ÏÙÚÔ ÊÚ ÛÎÔ Ú ÛÙÔ ÚÔ Ê ÏÙÚÔ Ó ÛÙ ÙÔ º ÏÙÚÔ Ó ÓÔÙÈÙ Ó Ô ÁÈ ÂÍ ÂÚÈÛÌfi ÌÂ ÚˆÌ ÙÈÛÌfi Û ÁÎ ÓÙÚˆÛË ÛÎfiÓË ÛÙÔ Ï ÛÈÔ ÙÔ Ê ÏÙÚÔ 3 ƒ ıÌÈÛË È Îfi ÙË Â ÈÏÔÁ ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ƒ ıÌÈÛË È Îfi ÙË Â ÈÏÔÁ ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú 1 ÌÊ ÚÔÌË ÓÙ ÏÏ Á Ú ÁÔÚÂ Ì Ó 2 Í ÂÚÈÛÌfi ÁÔÚÂ Ì ÓÔ 3 ÂÈÙÔ ÚÁ ...

Page 9: ... isolation 3 Raccordement Et Fixation Du Tuyau De Échangeur d Air Bidirectionnel Dans le cas d un diamètre de ø25 Feuille d isolation Dans le cas d un diamètre de ø20 Veuillez insérer le tuyau échangeur d air bidirectionnel jusqu à l extrémité de la sortie Feuille d isolation Extrémité de la sortie d échange d air bidirectionnel Manchon 2 Réglage De La Longueur Du Tuyau De Échangeur d Air Bidirect...

Page 10: ...de la pièce d installation de l appareil intérieur et vérifiez si la télécommande fonctionne correctement Si vous appuyez pendant une ou plusieurs secondes sur l interrupteur de service le fonctionnement de refroidissement par air forcé se déclenche Utilisez ce mode pour effectuer le diagnostic de panne ou la récupération du fluide réfrigérant dans l appareil extérieur Vis Capot Interrupteur de se...

Reviews: