– 93 –
MODEL RAC
-
18YH4
1. Turn off the power switch.
2. Remove the electrical box cover.
3. Turn on the power switch
4. After waiting for 30 seconds, push the service switch for a second.
LD303 (red) will light and the unit will operate in the forced cooling mode at this time.
Never operate the unit for
more than 5 minites.
(Cautions)
(1) If interface signal (DC 35V) terminals C and D are not connected when the outdoor unit is in forced cool mode,
the outdoor unit defect indicator (LD301) will blink 9 times during operation to indicate communication error.
(2) If checking is done with the compressor connector disconnected, the unit will stop and LD301 will blink 4 times.
Be sure to push the service switch for a second again to stop the forced cool operation.
1. Connect the large dia. pipe side and small dia. pipe side service valve using a pipe.
Parts to be prepared
(1) Reducing union
2/8” (6.35 mm)
3/8” (9.52 mm)
(2) Copper pipe (2/8” and 3/8”)
Connect the small diameter service
value and the large diameter service
valve using the reducing union and
copper pipe as shown on the right.
Charge refrigerant of 300g
The operation method is the same as “How to operate using the connector to servicing the outdoor unit”.
Do not operate for more than 5
minutes
Electrical box cover
Unit top cover
Large dia. service valve
Reducing union
(2/8” and 3/8”)
Copper pipe
(2/8”)
Small diameter
service valve
Reversing
valve
Compressor
Outdoor unit
HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
after vacuuming ( 1)
1 The charging amount of 200g is equivalent to the load in normal operation.
Summary of Contents for RAC-18YH4
Page 21: ... 19 GRAM 18YH4 RAC 18YH4 CAUTION The marked parts are very important ones for safety ...
Page 23: ... 21 RAS 18YH4 MODEL ...
Page 24: ... 23 RAC 18YH4 MODEL H8 3 0 3 9 AX 8 T 1 0 ...
Page 27: ... 26 MAIN P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE MODEL RAC 18YH4 ...
Page 29: ... 29 button MODEL RAS 18YH4 BASIC MODE 31 33 33 33 37 35 ...
Page 35: ... 38 REFRIGERATING CYCLE DIAGRAM MODEL RAS 18YH4 RAC 18YH4 SUCTION TANK SUCTION TANK ...
Page 99: ...Printed in Japan TSK AW NO 0004E RAS 18YH4 RAC 18YH4 ...