4. TROUBLESHOOTING [Protective Device]
SELECT/WIDE
1
2
RESET
1
a
b
Air-Cooled
Water-Cooled
Press 14 times.
To display of various settings
Press once to go to
the next item.
Press once to go to
the previous item.
Return to discharge
pressure display.
Not used
(display only)
DCBL controller
shutdown history
Fan inverter
shutdown history
SELECT/WIDE
Discharge pressure display
①
Press the
SELECT/WIDE
button 14 times. "E6." and "E7."
are shutdown history of DCBL controller.
②
Press the
RESET
button. The indication on digital monitor
returns to discharge pressure display.
■
How to Identify the Failure Cause of E0.13 (DCBL controller Error) and E0.57 (Fan
Inverter Error) and Check the History
Note : DCBL controller is equipped with Vtype.
Fan inverter is equipped with air-cooled type.
Code
Fault type
Detection
Probable cause
E01*
Overcurrent
Software
Activation of current protection circuit
Lock of main motor
Rapid acceleration/deceleration
E02*
Hardware
E05
Overload
Activation of electronic thermal
Overload of main motor
E07* Overvoltage
Excessive voltage of the converter
Excessive voltage of power line
E09
Undervoltage
Voltage below the specifi ed level
Reduction of receiving voltage, IPS
E10
CT error
CT error
E20
Temperature trip
Controller fan error
Reduction of controller fan revolution, disconnection of controller fan wiring
E21
Temperature trip
Overheat of cooling fi n
Cooling fi n, air intake hole, clogging of cooler, high ambient temperature
E22* Communication error 1 Communication error in controller
Electrical noise
E23* Gate array error
Gate array communication error
E24
Phase lacking
Phase lacking
E30
IGBT error
Occurrence of instantaneous overcurrent
E33
Communication error 2 Communication error between controller and PC board Electrical noise
E35
Main motor overheat
Excessive temperature of main motor
Cooling fi n, air intake hole, clogging of cooler, high ambient temperature
(a) Controller shutdown code
If the shutdown code “XX” is “
,” it indicates that
there is no shutdown history. Also, when anything
other than shutdown history is displayed without
shutdown resetting, the display is return to the latest
shutdown history in 3 minutes.
IMPORTANT
For the shutdown history of controller, only the most
recent shutdown is recorded. Shutdown history is
displayed in shutdown codes.
(
See the shutdown code list in this page.)
IMPORTANT
(b) Fan inverter shutdown code
Air-Cooled
Code
Fault type
Detection
Probable cause
E01*
Overcurrent
During constant speed
Activation of current protection circuit
Lock of fan motor
Rapid acceleration/deceleration
E02*
During deceleration
E03*
During acceleration
E04*
Other
E05
Overload
Activation of electronic thermal
Overload of fan motor, restart immediately after stop
E07* Overvoltage
Excessive voltage of the converter
High receiving voltage
E08
EEPROM error
Error data of EEPROM
Exogenous noise, temperature increase
E09* Undervoltage
Voltage below the specifi ed level
Low receiving voltage
E11
CPU error
Error of built-in CPU
E14
Ground fault
Ground fault during power activation
Between output and fan motor
E15
Overvoltage
Excessive voltage at no output
Receiving voltage is higher than specifi ed.
E21
Temperature trip
Temperature error
Cooling fi n, air intake hole, clogging of cooler, high ambient temperature
E23
Gate array error
Gate array communication error
E60
Communication error
Communication error between inverter and PC board Disconnection of communication line, exogenous noise
* Items subject for retry.