- 8 -
Table 4.2 Applicable wires
Model
Connection
resistance
Wire for P, RB, and
N connections (Note1)
SL1, SL2,
MA1, MA2
Grounding wire
E2-30K
8
Ω
or more
5.5mm
2
or more
0.75mm
2
or more
5.5mm
2
or more
5
Ω
to 7.9
Ω
8mm
2
or more
4
Ω
to 4.9
Ω
14mm
2
or more
E2-55K
4
Ω
or more
14mm
2
or more
3
Ω
to 3.9
Ω
22mm
2
or more
200V class
2
Ω
to 2.9
Ω
38mm
2
or more
EZ2-30K
17
Ω
or more
3.5mm
2
or more
13
Ω
to 16.9
Ω
5.5mm
2
or more
10
Ω
to 12.9
Ω
8mm
2
or more
EZ2-55K
10
Ω
or more
8mm
2
or more
7.5
Ω
to 9.9
Ω
14mm
2
or more
6
Ω
to 7.4
Ω
22mm
2
or more
EZ2-110K
6
Ω
or more
22mm
2
or more
4
Ω
to 5.9
Ω
38mm
2
or more
400V class
3
Ω
to 3.9
Ω
60mm
2
or more
Note 1:
The wire for P, RB, and N connections should be MLFC wire (flame-retardant poly-flex wire, able to withstand
voltage of 600 V).
If the distance between the dynamic braking unit and a discharging resistor is 10 meters or more, use a cable
thicker than the specified wire size. Table 4.2 shows sizes of MLFC wire.
-1) If the distance is between 10 m (not including 10 m) and 25 m, use a wire size one rank larger.
-2) If the distance is between 25 m (not including 25 m) and 50 m, use a wire size two ranks larger.
However, the cable should be up to 5 m between the braking unit and the discharging resistor.