When using the remote control switch ( ) or the
automatically recognized as the slave unit of the indoor unit #2 and
unit is not required. However, the contents of the setting should be checked.)
#
When using other controllers than the described above, the indoor unit can not be recognized as the slave unit
automatically, and set as the master unit of group 5. In this case change the setting to the slave unit of the group
3 according to the above "Group Setting Procedure".
Case 1: System of Less Than 16 Indoor Units Connected, Refrigerant System Address and Indoor Unit Address
The group is automatically set as zone No. 1 by the indoor unit address regardless of the refrigerant cycle address.
Set the indoor unit address without duplication of address.
Setting of
Indoor Unit RSW
Group No.
The address setting "0" to "15"
or "0" to "F" of indoor unit is
corresponding to the group No.
"1" to "16" of central station.
(The setting can be changed by
the procedure of "2. System of
More Than 17 Indoor Units
Connected".)
0
1
2
3
4
1
2
3
*
5
Central
Station
Case 2:
System of More Than 17 Indoor Unit Connected
In this case, the group setting by central
station is required. Group setting is for
master unit (directly connected to remote
control switch) and slave unit (connected
by extension cable).
In case that the remote control switch is
not connected, the group setting by
remote control switch is not available and
only one master unit is controlled as one
group.
In case of up to 16 indoor units connected,
the group setting is automatically
performed as described in "1. System of
Less Than 16 Indoor Units Connected,
Refrigerant System Address and
Indoor Unit Address". In this case,
correct the group setting by the
next page procedure.
Without Remote
Control Switch
Master
Slave
Master
Master
Slave
Master
Refrigerant No. Setting
1
1
2
2
3
3
Indoor Unit RSW Setting
0
1
0
1
0
1
Group No.
1
2
3
4
Central
Station
!
Group Setting Procedure
- The group setting consists of the master unit setting and the slave unit setting. The indoor unit, which is connected
directly to the remote control switch, is set as the master unit, and the indoor unit connected with the transmission
line is set as the slave unit.
- Without the remote control switch, the control by the remote control switch group is not available.
Therefore, in this case, one indoor unit is set as one group. (Only the master unit is set without the slave unit.)
- When setting the remote control switch group without transmission line between indoor units, the indoor unit
connected with the remote control switch shall be set as master unit.
- When using the remote control switch ( ) or receiver kit
central station automatically set the slave unit.
Check for the setting state by the slave unit setting mode.
HYXE
‐
A01H
(HYRE-V01H), after the setting of master unit, the
HYXE
‐
A01H
receiver kit (HYRE-V01H), the indoor units are
set to the group 3. (The setting of the slave
HYJE-D02H
125
Summary of Contents for HYE-W01
Page 7: ......
Page 9: ......
Page 16: ...Model HYXE J01H Wired Remote Control Switch 7 ...
Page 22: ...Model HYDE E01H 7 Day Timer 13 ...
Page 24: ...Model HCCS H128H2C1YM HCCS H128H2C1NM Central Control 15 ...
Page 25: ...Model HCCS H247R4C1E Central Control 16 ...
Page 26: ...Model HYJ J01H Central Control 17 ...
Page 27: ...Central Control Model HYJM S01H 18 ...
Page 34: ...HYXE G01H 25 ...
Page 35: ...HYXE G01H 26 ...
Page 46: ...HYXE J01H 37 ...
Page 47: ...HYXE J01H 38 ...
Page 48: ...HYXE J01H 39 ...
Page 49: ...HYXE J01H 40 ...
Page 50: ...HYXE J01H 41 ...
Page 51: ...HYXE J01H 42 ...
Page 52: ...HYXE J01H 43 ...
Page 53: ...HYXE J01H 44 ...
Page 54: ...HYXE J01H 45 ...
Page 55: ...HYXE J01H 46 ...
Page 56: ...HYXE J01H 47 ...
Page 57: ...HYXE J01H 48 ...
Page 58: ...HYXE J01H 49 ...
Page 59: ...HYXE J01H 50 ...
Page 60: ...HYXE J01H 51 ...
Page 61: ...HYXE J01H 52 ...
Page 62: ...HYXE J01H 53 ...
Page 63: ...HYXE J01H 54 ...
Page 64: ...HYXE J01H 55 ...
Page 65: ...HYXE J01H 56 ...
Page 66: ...HYXE J01H 57 ...
Page 67: ...HYXE J01H 58 ...
Page 68: ...HYXE J01H 59 ...
Page 69: ...HYXE J01H 60 ...
Page 70: ...HYXE J01H 61 ...
Page 71: ...HYXE J01H 62 ...
Page 72: ...HYXE J01H 63 ...
Page 73: ...HYXE J01H 64 ...
Page 74: ...HYXE J01H 65 ...
Page 75: ...HYXE J01H 66 ...
Page 76: ...HYXE J01H 67 ...
Page 115: ...HYDEͲE01H Hisense HYDE E01H 106 ...
Page 116: ...HYDE E01H 107 ...
Page 117: ...HYDE E01H 108 ...
Page 119: ...HYXE A01H HYJE D02H HYXE A01H HYXE A01H HYXE A01H HYJE D02H HYJE D02H HYJE D02H HYDE E01H 110 ...
Page 120: ...HYXE A01H HYJE D02H HYDE E01H 111 ...
Page 121: ...HYDE E01H 112 ...
Page 122: ...HYDE E01H 113 ...
Page 123: ...HYDE E01H 114 ...
Page 124: ...HYXE A01H HYJE D02H HYDE E01H 115 ...
Page 125: ...HYXE A01H HYJE D02H HYDE E01H 116 ...
Page 126: ...HYJE D02H HYDE E01H 117 ...
Page 127: ...HYDE E01H 118 ...
Page 128: ...HYJE D02H HYXE A01H HYDE E01H 119 ...
Page 129: ...HYJE D02H HYJE D02H HYXE A01H Hisense Hisense HYDE E01H 120 ...
Page 173: ...HYJ J01H 164 ...
Page 174: ...HYJ J01H 165 ...
Page 175: ...HYJ J01H 166 ...
Page 176: ...HYJ J01H 167 ...
Page 177: ...HYJ J01H 168 ...
Page 178: ...HYJ J01H 169 ...
Page 179: ... R QRW KDV WKLV IXQFWLRQ DV HW HYJ J01H 170 ...
Page 180: ...HYJ J01H 171 ...
Page 181: ...HYJ J01H 172 ...
Page 182: ...HYJ J01H 173 ...