43
Alarm Management
The alarms in RWR470.10 are divided into two groups: auto reset alarms and manual
reset alarms.
1.
Auto reset alarm, the user is not required to acknowledge and reset it.
2.
The corresponding device will be automatically restarted once the alarm status
disappears.
3.
Once a manual reset alarm is detected, the system will be stopped automatically.
The user needs to record and contact the supplier on actions what to do.
4.
To acknowledge and reset the alarm press the <Enter> button.
5.
Ensure that the fault has been fixed before the alarm has been reset.
When an alarm is detected:
The corresponding device icon (if any) and the
icon will continuously flash.
An alarm code will be displayed on the screen.
If more than one alarm is detected, the alarm codes will be displayed successively
on the LCD screen. These will be seen by using the <plus> or <minus> buttons,
or they are manually acknowledged or reset (only for manual reset alarms).
If the system detects warnings and alarms at the same time, the warning codes will
NOT be displayed on the LCD screen.
The last 20 auto alarms and manual reset alarms generated in total are separately
logged under the auto reset alarm (AR) and manual reset alarm (MR) categories in
the
menu.
Note:
The log is lost if the unit has a power de-powered.
Warning and Alarm