Each relay is configurable to:
• change states based on any alarm condition or status point
• be latching or non-latching
• switch to active state after a pre-programmed delay
Binary Inputs
Binary Inputs
The four (4) Binary Inputs are optically isolated from ATevo and each other. They can be
configured via jumper selection to accept input voltages of 12Vdc, 24Vdc, 48Vdc, or
130Vdc. Each Binary Input has an associated yellow LED and a jumper selection block. The
LED serves as a debugging aid as it will illuminate when the associated Binary Input is high
(in the ‘ON’ state).
The Binary Inputs may be configured to be active high or active low and generate alarms
and controls such as charger shutdown. The configuration also permits each input to be
assigned a custom name (such as ‘2% Hydrogen’, or ‘Vent Fan Fail’). ATevo will report all
activity of the input (status, alarms or log files) by the generic default name or the custom
configured name.