X-AO 16 01
4 Start-up
HI 801 111 E Rev. 4.00
Page 37 of 52
4.3.4 Submodule
Status [DWORD]
Coding of the
Submodule Status
Coding
Description
0x00000001
Fault in hardware unit (submodule)
0x00000002
Reset of an E/A bus
0x00000004
Faults detected while configuring the hardware
0x00000008
Fault detected while verifying the coefficients
0x00000010
First temperature threshold exceeded (warning temperature)
0x00000020
Second temperature threshold exceeded (limit temperature)
0x00000040
Module shutdown due to overcurrent
0x00000080
Reset of the chip select monitoring
Table 22: Submodule Status [DWORD]