System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 75 of 114
Name
Explanation
Port
Port number as printed on the housing; per port, only one
configuration may exist.
Range of values: 1...n, depending on the resource
Speed [Mbit/s]
10 Mbit/s: Data rate 10 Mbit/s
100 Mbit/s: Data rate 100 Mbit/s
Autoneg (10/100): Automatic baud rate setting
Standard: Autoneg
Flow Control
Full duplex: Simultaneous communication in both directions
Half duplex: Communication in both directions, but only one
direction at a time
Autoneg: Automatic communication control
Standard: Autoneg
Autoneg also with fixed
values
The
Advertising
function (forwarding the Speed and Flow Control
properties) is also performed if
Speed
and
Flow Control
have
fixed values.
This allows other devices with ports set to
Autoneg
to recognize
the HIMatrix ports' settings.
Limit
Limit the inbound multicast and/or broadcast packets.
Off: No limitation
Broadcast: Limit broadcast packets (128 kbit/s)
Multicast and Broadcast: Limit multicast and broadcast packets
(1024 kbit/s)
Default: Broadcast
Table 41: Port Configuration Parameters - CPU OS and Higher
To modify and enter these parameters in the communication system's configuration, double-
click each table cell. The parameters become operative for HIMatrix communication, once they
have been re-compiled with the user program and transferred to the controller.
The properties of the communication system and Ethernet switch can also be changed online
using the Control Panel. These settings become operative immediately, but they are not
adopted by the user program.
Refer to the SILworX communication manual (HI 801 101 E) for more details about configuring
safe
ethernet
.
7.6
Configuring Alarms and Events - with CPU 03
Event Definition
1. Define a global variable for each event. Generally use global variables that have already
been defined for the program.
2. Below the resource, create a new
Alarms&Events
branch, if not existing.
3. Define events in the A&E Editor.
-
Drag global variables into the event window for Boolean or scalar events.
-
Define the details of the events, see the following tables.
The events are defined.
For further information, refer to the SILworX online help.