F3 DIO 20/8 02
4 Start-up
HI 800 345 E Rev. 2.00
Page 33 of 48
4.3.3.2
Tab
DO 8: Channels
The
DO 8: Channels
tab contains the following system parameters.
System
parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital output channels
Coding
Description
0x01
Fault in the digital output module
0x02
Channel shutdown due to overload
0x04
Error while reading back the digital outputs
0x08
Error while reading back the status of the digital
outputs
0x40
External short-circuit or short-circuit of the EMC
protection returns an error
0x80
Channel is switched off due to fault on the
corresponding channel
Value [BOOL]
->
BOOL
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Table 25: SILworX - System Parameters for Digital Outputs,
DO 8: Channels
Tab
Summary of Contents for HIMatrix F3 DIO 20/8 02
Page 47: ......