F3 DIO 20/8 02
4 Start-up
HI 800 345 E Rev. 2.00
Page 27 of 48
4.1.3
Cable Plugs
Cable plugs attached to the pin headers of the devices are used to connect to the power supply
and to the field zone. The cable plugs are included within the scope of delivery of the HIMatrix
devices and modules.
The devices power supply connections feature the following properties:
Connection to the power supply
Cable plugs
Four poles, screw terminals
Wire cross-section
0.2…2.5 mm
2
(single-wire)
0.2…2.5 mm
2
(finely stranded)
0.2…2.5 mm
2
(with wire end ferrule)
Stripping length
10 mm
Screwdriver
Slotted 0.6 x 3.5 mm
Tightening torque
0.4…0.5 Nm
Table 20: Power Supply Cable Plug Properties
Connection to the field zone
Number of cable plugs
7 pieces, six poles, screw terminals
Wire cross-section
0.2…1.5 mm
2
(single-wire)
0.2…1.5 mm
2
(finely stranded)
0.2…1.5 mm
2
(with wire end ferrule)
Stripping length
6 mm
Screwdriver
Slotted 0.4 x 2.5 mm
Tightening torque
0.2…0.25 Nm
Table 21: Input and Output Cable Plug Properties
Summary of Contents for HIMatrix F3 DIO 20/8 02