F3 DIO 20/8 02
4 Start-up
HI 800 345 E Rev. 2.00
Page 25 of 48
4 Start-up
To start up the remote I/O, it must be mounted, connected and configured in the programming
tool.
4.1
Installation and Mounting
The remote I/O is mounted on a 35 mm DIN rail such as described in the HIMatrix system
manual for compact systems.
When laying cables (long cables, in particular), take appropriate measures to avoid interference,
e.g., by separating the signal lines from the power lines.
When dimensioning the cables, ensure that their electrical properties have no negative impact
on the measuring circuit.
4.1.1
Connecting the Digital Inputs
Use the following terminals to connect the digital inputs:
Terminal
Designation
Function (inputs)
13
LS+
Sensor supply of the inputs 1...4
14
1
Digital input 1
15
2
Digital input 2
16
3
Digital input 3
17
4
Digital input 4
18 L- Ground
Terminal
Designation
Function (inputs)
19
LS+
Sensor supply of the inputs 5...8
20
5
Digital input 5
21
6
Digital input 6
22
7
Digital input 7
23
8
Digital input 8
24 L- Ground
Terminal
Designation
Function (inputs)
25
LS+
Sensor supply of the inputs 9...12
26
9
Digital input 9
27
10
Digital input 10
28
11
Digital input 11
29
12
Digital input 12
30 L- Ground
Terminal
Designation
Function (inputs)
31
LS+
Sensor supply of the inputs 13...14
32
13
Digital input 13
33
14
Digital input 14
34
15
Digital input 15
35
16
Digital input 16
36 L- Ground