F2 DO 8 01
4 Start-Up
HI 800 157 E Rev. 1.01
Page 25 of 40
4.3.2.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data
type
R/W Description
DO.Error Code
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001 Module
fault.
0x0002
MOT test safety switch 1 faulty
0x0004
MOT test safety switch 2 faulty
0x0008
FTT test of test pattern faulty
0x0010
MOT test of the read back channels faulty
0x0020
MOT test active shutdown faulty
0x0040
Errors during initialization: relay
0x0080
FTT test: error in the relay voltage
0x0100
FTT test of CS (chip select) signals faulty
0x0400
FTT test: 1st temperature threshold
exceeded
0x0800
FTT test: 2nd temperature threshold
exceeded
0x1000
MOT test: status of safety switch 1
0x2000
MOT test: status of safety switches
0x4000
MOT test: active shutdown via watchdog
faulty
Module Error Code WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (remote I/O not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: incorrect configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x003C [60
dec
]
Table 15: SILworX - System Parameters for Relay Outputs,
Module
Tab