Configuring Gateway
43/72
SmartWire-DT Gateway | EU5C-SWD-POWERLINK
DOC130802UM02EN | Revision 2 | English | 2013-12 | Released | Public
© Hilscher 2013
Prerequisites for reading-in the SmartWire-DT configuration are:
All SmartWire-DT slaves are connected to the SmartWire-DT line.
The SmartWire-DT network is connected to the gateway.
The voltage POW is applied to the gateway and the power LED POW is
on.
The voltage AUX is applied (if necessary).
The SmartWire-DT status LEDs of the individual SmartWire-DT slaves
are on or are flashing.
The POWERLINK network is disconnected from the gateway by
removing the RJ45 plug from the Ethernet interface of the gateway.
To read-in the SmartWire-DT configuration proceed as follows:
Make sure that POWERLINK is disconnected from the gateway.
Press the configuration button on the gateway for at least two seconds
(for the position of the configuration button, see figure
Front View
EU5C-SWD-POWERLINK Gateway
on page 27).
Note
:
Take care to push-in the button properly. You have to feel and
overcome a slight resistance at the end when pushing the button into the
gateway, otherwise the button won’t trigger.
The SmartWire-DT status LED (SWD LED) on the gateway begins to
flash orange. The SmartWire-DT status LEDs on the SmartWire-DT
slaves also flash. All slaves are addressed in sequence, the complete
configuration is stored retentively as gateway target configuration.
The SmartWire-DT status LED (SWD LED) on the gateway shows
steady green.