Ex
Explosion-proof Dome
·
Quick Start Guide
v
ATEX:
II 2GD Ex db IIC T6 Gb /Ex tb IIIC T80
℃
Db IP68
IECEx: Ex db IIC T6 Gb /Ex tb IIIC T80
℃
Db IP68
Hazardous Area Classification: Zone 1, Zone 2, Zone 21, Zone 22
IP Degree: IP68 (2m, 2h)
Ex Standards:
IEC 60079-0: 2011 EN 60079-0: 2012
IEC 60079-1: 2014 EN 60079-1: 2014
IEC 60079-31: 2013 EN 60079-31: 2014
Special Conditions for Safe Use
1.
Ambient temperature: -40
°C
- +60
°C
2.
DO NOT OPEN WHEN ENERGIZED
3.
POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS
4.
When assembly, operation and maintenance, the operator must follow the
requirements of the IEC 60079-14: latest version Explosive atmospheres- Part 14:
Electrical installations design, selection and erection, beside of the manufacturer’s
operating instructions or its National equivalent.
5.
Repair and overhaul shall comply with IEC 60079-19: latest version or its National
equivalent.
Explosion-proof Dome Nameplate
Explosion-proof Dome
WARNING: DO NOT OPEN WHEN ENERGIZED
CAUTION : USE FASTENERS WITH YIELD
STRENGTH
≥
450MPa
POTENTIAL ELECTROSTATIC CHARGING
HAZARD-SEE INSTRUCTIONS