In a conditions of non-working status of the device, the horizontal and vertical vibration
acceleration value of the floor surface of equipment room must be lower than 0.5 m/S².
The rack or surface on which the device is installed must be properly grounded, and
ensure that each device is grounded as well. The resistance between the device casing
and the ground must be less than 4 Ω.
According to the requirements of ANSId/ISAe-71.04-1985 gas corrosion grade G1, the
corrosion rate of copper test piece must be less than 300 Å c/month.
Å is the length unit. 1 Å equals to 1/1 billion meter.
ANSI refers to American National Standards Institute, and ISA refers to Instrument Society
of America.
The temperature and humidity requirements:
Working temperature: 5 °C to 40 °C (41 °F to 104 °F);
Equipment room temperature: 23 °C ± 2 °C (73.4 °F ±
35.6 °F);
Storage temperature: -40 °C to 55 °C (-40 °F to 131 °F);
Transportation temperature: -40 °C to 70 °C (-40 °F to 158 °F);
Temperature change rate: < 5 °C (41°F)/h (noncondensing);
Working humidity: 20% RH to 80% RH;
Storage humidity: 5% RH to 95% RH;
Transportation humidity: 5% RH to 95% RH
1.2 Installation and Initial Power-on
The device shall be placed on the fixed flat surface. Tilting surface is not allowed.
You can use the standard plate in the industrial cabinet or use the guide rail (not provided) to
install the device to the rack. It is recommended to use the bolts to fix the device to the rack
through the mounting screw holes on the rack.
Connect all the power cords of the device to the power socket and wait for 12 hours before
starting up. The temperature of the device and the equipment room must be consistent to
prevent the damage caused by a huge temperature difference.
If the device has been transported and stored for more than 10 days; perform the previous
operation and then start up and run the device for 30 minutes without the hard disks. And
then you shut down the device, insert the hard disks and start the device again.
1.3 Notes for Installation
The device is a high-precision equipment. Please keep stable and gentle when moving it.
Installation and running environment must meet standards. Take regular investigations and
records for the equipment room, or apply a remote monitoring for the working status of the
device.