Appendix 3 24 VAC Wire Gauge and Transmission Distance
The following table describes the recommended maximum distance adopted for a specific wire gauge
when the 24 VAC voltage loss rate is less than 10 percent. For an AC-driven device, the maximum allowed
voltage loss rate is 10 percent. For example, for a device with a rating power of 80 VA, which is installed at
a distance of 35 feet (10 m) away from the transformer, 0.8000 mm is required as the minimum wire gauge.
Distance Wire Gauge
(feet)
(mm)
Power (VA)
0.8000
1.000
1.250
2.000
10
283(86)
451(137)
716(218)
1811(551)
20
141(42)
225(68)
358(109)
905(275)
30
94(28)
150(45)
238(72)
603(183)
40
70(21)
112(34)
179(54)
452(137)
50
56(17)
90(27)
143(43)
362(110)
60
47(14)
75(22)
119(36)
301(91)
70
40(12)
64(19)
102(31)
258(78)
80
35(10)
56(17)
89(27)
226(68)
90
31(9)
50(15)
79(24)
201(61)
100
28(8)
45(13)
71(21)
181(55)
110
25(7)
41(12)
65(19)
164(49)
120
23(7)
37(11)
59(17)
150(45)
130
21(6)
34(10)
55(16)
139(42)
140
20(6)
32(9)
51(15)
129(39)
150
18(5)
30(9)
47(14)
120(36)
160
17(5)
28(8)
44(13)
113(34)
170
16(4)
26(7)
42(12)
106(32)
180
15(4)
25(7)
39(11)
100(30)
190
14(4)
23(7)
37(11)
95(28)
200
14(4)
22(6)
35(10)
90(27)
Appendix 4 Wire Gauge Standards
Bare Wire
Gauge (mm)
America Wire
Gauge AWG
British Wire
Gauge SWG
Cross-Sectional
Area of Bare
Wire (mm
2
)
0.750
21
0.4417
0.800
20
21
0.5027
0.900
19
20
0.6362
1.000
18
19
0.7854
1.250
16
18
1.2266
1.500
15
17
1.7663
2.000
12
14
3.1420
2.500
4.9080
3.000
7.0683