USER'S GUIDE R14 AXIAL FAN , Code: 0000, Iss: 21.09.2021

06

PUTTING INTO OPERATION

Before first start you should check:

a. Appropriate installation and electrical connection, especially resistance of the protective-earth (PE) circuit (max. 100m

).

b. If safety equipment is in place and motor protection device is in function.

c. If the impeller can rotate freely once the unit is mounted and the right direction of rotation is assured.

Only if all dangerous situations are excluded, the fan may be put into operation!

Switch ON the power supply.

Switch ON the device via the control signal and apply the speed setting voltage/signal and check the direction of the rotation and the smoothness of
running.

07

DIAGNOSTICS & TROUBLESHOOTING

Fan does not start or run - alarm rele status OPEN or FLASHES:
Possible causes: missing power (no line voltage), low voltage (under 320V), extremely thermally or mechanically overloaded or fan failure (short circuit
of electronic or windings).
Check line voltage, check value and polarity of control signal, check that rotor is free to rotate.

Fan does not start or run - alarm rele status CLOSE:
Possible causes: missing or inadequate control signal.
Check value and polarity of control signal.

Fan runs with half of desired speed - alarm rele status CLOSE:
Possible causes: Low supply voltage, inadequate control signal or fan overheating.
Check line voltage, check control signal, check temperature and sufficient airflow of cooling air or loss of motor cooling.

Attention !

In the event of fan failure is detected (short/open in circuit of electronics/windings), never try to repair the fan, but replace it with new one or return it to
the manufacturer for repair or replacement.

08

PROTECTIVE FEATURES

Short-circuit protection:

The motor and electronic has no protection functions against short circuit. Short-circuit protection must be provided with an external means - for
example with using a circuit breaker of max. 3x16A / 400V type B.

Locked-rotor protection:

As soon the rotor is blocked, the motor is switched off electronically. After de-blocking, the motor will restart automatically. 

Mains under voltage:

If mains voltage falls below the nominal value the motor will keep running with degraded performance. Below 320V, the motor will be switched off
electronically in stand-by mode. When mains voltage returns to correct value, the motor will restart automatically. 
In the specific case, the undervoltage protection may switch off the fan to stand-by mode, for example, fan running or testing at high pressure drop and
low voltage.

Over temperature protection:

Internally connected thermal overload protector to protect electronic and motor against over temperature.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

8 / 9

Summary of Contents for 0314-4-0166

Page 1: ...G INTO OPERATION 07 DIAGNOSTICS TROUBLESHOOTING 08 PROTECTIVE FEATURES 09 MAINTENANCE SERVICE AND CLEANING 10 TRANSPORT AND STORAGE 11 ErP ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL D...

Page 2: ...nnot cause serious damage or bodily harm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance...

Page 3: ...s appliance is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be...

Page 4: ...53 5 Installation category A Efficiency category static Efficiency grade N 60 3 Variable speed drive INTEGRATED Power Input Pelec 858 5 W Airflow volume qV 9867 m h Pressure Increase ps 161 Pa Rotati...

Page 5: ...that the air gap between the fan impeller and the stationary housing is constant Distortion due to an uneven surface of basis may lead to a fan failure Air gap between blade and cone inlet housing sh...

Page 6: ...ss of water or moisture inside the terminal box If the cable is not installed through the cable gland sealing plug must remain in the gland Secure connection cable to the fan guard grill or to the mot...

Page 7: ...ighest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to ac...

Page 8: ...upply voltage inadequate control signal or fan overheating Check line voltage check control signal check temperature and sufficient airflow of cooling air or loss of motor cooling Attention In the eve...

Page 9: ...orce for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans i...

Reviews: