USER'S GUIDE R14 AXIAL FAN , Code: 0000, Iss: 21.09.2021

03

OPERATING CONDITIONS

The fans are rated for S1 (IEC 60034-1) continuous operation.

Extreme ON-OFF switching operating must be avoided, because it has negative influence on life expectancy and power consumption.

Cycling operating mode should only with cycling ON/OFF via control signal (0/10V analog input or PWM input).

Do not cycling the power supply for cycling operating mode – use control signal! High 'In-rush current' can occur during cycling power supply!

Permissible ambient temperature is stated to the specified operating points - see appended 'Performance curves' for actual fan. If actual load deviates
from specified operating point, motor temperature-rise should be checked.

Figures on the motor name-plate refer to nominal values according to rule specified on the nameplate next to the written values. The rules (EN_60335,
'free air', 'max.load', 'max.eff.',  cust. unit / cust. spec., UL, IEC 60034-1) are described in the example shown below.

Continuous sound pressure level may exceed 70dBA (depends of fan model).

If an already installed fan is switched OFF for a long period in a humid atmosphere, it should be switched ON for minimum of two hours every month to
remove any moisture that may have condensed inside the motor.

Protection (motor & electronics): IP54 according to EN60529.

Power consumption in stand-by mode: les than 5W.

DIMENSIONS 

Nominal diameter: 630 mm - see Appendix - technical drawing: VENTILATOR / R14R-63APS-ET80B-10C17

Weight: 16 kg 

 NOMINAL DATA - defined according to ' IEC 60335 '

Phase: 3~

Nominal Voltage: 400 V

Operating Voltage range: 380-480 V

Frequency: 50-60 Hz

Input power: 820 W

Nominal current: 1,5 A

Rotational speed: 1100 RPM

Operating ambient temperature range: -25°C .. +60°C

Altitude: 2000 m

Insulation class: 155

Protection provided by PE: Class I 

Overvoltage category (OVC):  

Operating humidity ambient: up to 95% (non condensing).

Max. pressure: 160 Pa

ErP DATA

Overall Efficiency, Effes: 53,5 %

Installation category: A

Efficiency category: static

Efficiency grade, N: 60,3

Variable speed drive: INTEGRATED

Power Input , Pelec: 858,5 W

Airflow volume , qV: 9867 m³/h

Pressure Increase, ps: 161 Pa

Rotational Speed, n: 1109 RPM

Specific ratio: 1,002

Airflow volume max., qV: 13366 m³/h

Pressure Increase max., ps: 444 Pa

1. Fan type and code
2. Trade mark and manufacturer address
3. Nominal values (Voltage, frequency, Electric Power, Current...)
4. Certification marks
5. Date of production (week of the year/year)
6. QR code which includes code number, production date, serial number 
and link to website.
7. Data acc. to EU regulation 327/2011 (ErP)
8. NOTE INDICATE TO WHICH STANDARD/RULES CORESPOND DATA ON THE 
NAMEPLATE:

- EN 60335-1 

: Name-plate data are made according to standard EN 

60335-1, Household and similar electrical appliances – Safety – Part 1, 
Articles 10.1 and 10.2:
If an appliance is marked with rated power input, the power input at 
normal operating temperature shall not deviate from the rated power 
input by more than: + 20% if Pn<300W or  +15% (or 60W whichever is 
the greater)  if Pn>300W.
If an appliance is marked with rated current, the current at normal 
operating temperature shall not deviate from the rated current by more 
than: +20% if In<1.5A or  +15% (or 0,30A whichever is the greater)  if 
In>1.5A.

- FREE AIR

: Data on the nameplate established at a point 0Pa static 

pressure at normal operating temperature.

- MAX LOAD 

: Data on the nameplate established at a point of maximal 

static pressure regarding max. ambient 

temperature

.

- MAX. EFF. 

: Data on the nameplate established at a point of maximal 

static efficiency at normal operating temperature.

- CUST. UNIT / CUST. SPEC.

: Data on the nameplate specified according 

to customer specifications or at working point in customer's unit .

- UL

- Data on the nameplate defined according to specifications in UL 

standards.

- IEC 60034-1 

- Data on the nameplate established at a point of nominal 

load according to standard for Rotational electrical machines.

An example of a label and explanation of the content

:

1

2

5

6

7

8

3

4

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

4 / 9

Summary of Contents for 0314-4-0166

Page 1: ...G INTO OPERATION 07 DIAGNOSTICS TROUBLESHOOTING 08 PROTECTIVE FEATURES 09 MAINTENANCE SERVICE AND CLEANING 10 TRANSPORT AND STORAGE 11 ErP ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL D...

Page 2: ...nnot cause serious damage or bodily harm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance...

Page 3: ...s appliance is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be...

Page 4: ...53 5 Installation category A Efficiency category static Efficiency grade N 60 3 Variable speed drive INTEGRATED Power Input Pelec 858 5 W Airflow volume qV 9867 m h Pressure Increase ps 161 Pa Rotati...

Page 5: ...that the air gap between the fan impeller and the stationary housing is constant Distortion due to an uneven surface of basis may lead to a fan failure Air gap between blade and cone inlet housing sh...

Page 6: ...ss of water or moisture inside the terminal box If the cable is not installed through the cable gland sealing plug must remain in the gland Secure connection cable to the fan guard grill or to the mot...

Page 7: ...ighest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to ac...

Page 8: ...upply voltage inadequate control signal or fan overheating Check line voltage check control signal check temperature and sufficient airflow of cooling air or loss of motor cooling Attention In the eve...

Page 9: ...orce for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans i...

Reviews: