background image

© 2018 HID Global Corporation All rights reserved.

 

Installation Guide 

Page 11 of 26

 

Web-Based Access Control Solution

 

ACW2-XN 

 

 

Controller Module 

Cable Specifications 

Application  Conductors 

Cross Section  Max Cable  

Length 

Network 

>=  0,75 mm

2

 

150 m 

RS-485 

Twisted pair, with or without screen  >=  0.51 mm

2

 

1 000 m  

Key Components and Connections 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: 

 

Any module that has changes made to its DIP Switch settings while already powered up must be 

powered down and powered up again. This is because the settings are only read by the module 

during the power up cycle. 

 

DIP-switch Position 

Function MODE 

 

0000 

Slave Controller Mode  

 

0100 

Master Controller Mode 

RJ45 Network Socket 

12 VDC Supply  

(Pre-Wired) 

Device RS-485 Terminal 

This is used for linking 

the Master Controller to 

the Slave Controller 

Enclosure Anti-Tamper 

(Pre-Wired) 

DIP Switches 

Factory set for 

Master (0100) 

Host RS-485 Terminal 

Reserved for future expansion 

Battery Tag 

REMOVE before   

powering up the system 

Earthing Terminal 

(See page 12 for details) 

Summary of Contents for ACW2-XN

Page 1: ...ost or stolen credentials Use a standard web browser to access the intuitive management portal The web based portal HID Access Manager makes it convenient to provision and revoke smart cards without t...

Page 2: ...s per Person Max Logs 100 000 events of Doors 2 Doors or 1 APB Door Expandable to 16 doors or 8 APB Doors Note 1 Additional ACW2 XN and or AW2 modules are required 2 See System Architecture Best Pract...

Page 3: ...ler Module with an uncrossed network cable Suggested Tools Electric drill Drill bits Masonry steel to suite the site wall materials Screwdriver small flat Wire strippers Side cutters Site plan to lay...

Page 4: ...The two enclosures are linked with an RS 485 cable saving on long multiple reader cable runs Remember that the total door count still cannot exceed the 16 door limit How many AW2 Modules are needed On...

Page 5: ...hts reserved Installation Guide Page 5 of 26 Web Based Access Control Solution ACW2 XN 16 Reader 8 APB Door Example Note HID Access Manager will only accommodate 16 doors in total Master and Slave Con...

Page 6: ...ons NOTE that the Slave ACW2 XN Does NOT connect to the network MUST connect via RS 485 to the Master ACW2 XN Is able to continue reading cards and controlling its doors in the event of an RS 485 cabl...

Page 7: ...as per instructions above 7 Mount the enclosure to the surface 8 Replace the lid and plug the lid cable back in after the system wiring is complete 9 Place the AC and AW2 module labels in the correct...

Page 8: ...0 150 m 492 ft MOV included in the packaging Specification MOV Rating 25VRMS 500A 77VMax Clamping Where to use the suppled MOVs The MOVs MUST be connected across 12V inductive loads to prevent sparkin...

Page 9: ...IP switch Position Function 1110 Factory Set DIP Switch Position Wiegand 26 bit 44 bit 40 bit 37 bit and card PIN code Mode Module Data LED Relay 1 Terminals Relay 2 Terminals Wiegand Reader 1 Termina...

Page 10: ...egand Module are connected across any inductive loads NB The supplied MOVs are only suitable for 12V applications CAUTION Inadequate spark suppression can result in early failure of relay contacts and...

Page 11: ...ngs while already powered up must be powered down and powered up again This is because the settings are only read by the module during the power up cycle DIP switch Position Function MODE 0000 Slave C...

Page 12: ...wnload from the More Documentation link included on page 2 Earthing Terminal The Controller and Wiegand Modules are sensitive to Electrostatic Discharges ESD Observe precautions while handling the cir...

Page 13: ...wire end into its corresponding terminal 5 Releasing the terminal button will clamp the stripped wire end in place 6 Take some time to thoroughly inspect all the wiring and correct any mistakes before...

Page 14: ...ersion 10 1 1 Android 6 Windows 7 DNS Name function The DNS Name function only works with a PC If you wish to use DNS feature with mobile phones then you need to set the DNS setting within your WLAN r...

Page 15: ...ress 1 Click Start Control Panel 2 Click the Network and Sharing Centre icon 3 Select Local Area Connection 4 Click the Properties button 5 Double click Internet Protocol Version 4 TCP IPv4 6 Set the...

Page 16: ...ss Manager will open on the Live Screen Required Settings Using the menu driven interface paths shown on the next page complete these steps 1 Set the date and time 2 Update the master password 3 Add C...

Page 17: ...ettings Date and Time Security Changing the password Special Days Add public holidays etc Language Change language preference Preferencia cambiar idioma Advanced options o Access Groups o UDP output D...

Page 18: ...em wiring is complete and tested on the built in power supply Battery Specification Type Lead Gel Voltage 12V Capacity 7 Ah Physical Dimensions 65 mm x 101 mm x 151 mm 2 56 x 3 98 x 5 95 or smaller Ba...

Page 19: ...nductive loads see page 8 Inter Module Communications Connector Purpose 10 way connectors Female on the left male on the right Power and data lines to other modules Wiegand Reader Port Connector Reade...

Page 20: ...as intruders cannot just walk in when power is lost Which lock to use Mag locks are inherently Fail Safe as they require power to lock Strike locks are available in Fail Safe as well as Fail Secure v...

Page 21: ...ans that access control in the remote area will continue to function normally in the event of a break in the RS 485 cable The cable break event will logged on the ACW2 XN Master When the RS 485 cable...

Page 22: ...regoing license grant and terms and conditions of this EULA Licensee may make the Software and Documentation available to a third party to operate the Software on behalf of Licensee provided that Lice...

Page 23: ...on or in any copy made of the Software or Documentation 6 Warranty and Disclaimers 6 1 Limited Warranty HID warrants that for a period of ninety 90 days from the date the Software is delivered to Lice...

Page 24: ...b obtain for Licensee a license to continue using the Software or c if non infringing product or a license to use the Software cannot be obtained upon commercially reasonable terms as determined solel...

Page 25: ...ase order or other Licensee document usage or custom shall be deemed to amend or modify this EULA If any of these provisions are held to be unenforceable in any jurisdiction for any reason such provis...

Page 26: ...Page 26 of 26 Installation Guide 2018 HID Global Corporation All rights reserved Web Based Access Control Solution ACW2 XN 13 Notes...

Reviews: