© 1995-2009 Energy Saving Products Ltd.
Model: HE-50
# Outlets
12
16
20
24
Cooling: 5.3 kW
Mode
Airflow in L/s
Heating: 9.4 kW
Hi Cooling (Y2)
177 193 196 198
ESH: 5-10 kW
Lo Cooling (Y1)
106 116 118 120
Dehumid (D)
142 142 123 132
Hi Heating (W2)
160 168 160 170
Pin Setting 0001-0100
Lo Heating (W1)
130 132 123 127
Constant (G)
87
101 118 125
1
2
3
4
5
6
7
8
Model: HE-50
# Outlets
16
20
24
Cooling: 7.0 kW
Mode
Airflow in L/s
Heating: 11.7 kW
Hi Cooling (Y2)
231 238 245
ESH: 5-15 kW
Lo Cooling (Y1)
139 144 149
Dehumid (D)
193 196 198
Hi Heating (W2)
217 222 227
Pin Setting 0011-0100
Lo Heating (W1)
168 160 142
Constant (G)
123 120 139
1
2
3
4
5
6
7
8
Model: HE-50
ON
ON
Model: HE-70
# Outlets
24
28
32
Cooling: 10.6 kW
Mode
Airflow in L/s
Heating: 17 kW
Hi Cooling (Y2)
356 363 363
ESH: 5-18 kW
Lo Cooling (Y1)
215 219 219
Dehumid (D)
283 288 286
Hi Heating (W2)
321 328 326
Pin Setting 0110-0100
Lo Heating (W1)
255 257 255
Constant (G)
175 182 179
1
2
3
4
5
6
7
8
Model: HE-70
Model: HE-70
# Outlets
20
24
28
32
Cooling: 8.8 kW
Mode
Airflow in L/s
Heating: 15 kW
Hi Cooling (Y2)
293 307 311 316
ESH: 5-18 kW
Lo Cooling (Y1)
177 184 189 191
Dehumid (D)
241 248 250 245
Hi Heating (W2)
269 283 288 286
Pin Setting 0101-0100
Lo Heating (W1)
210 217 217 208
Constant (G)
146 165 175 175
1
2
3
4
5
6
7
8
ON
ON
Model: HE-100
# Outlets
36
40
44
48
Cooling: 17.6 kW
Mode
Airflow in L/s
Heating: 27.5 kW
Hi Cooling (Y2)
592 590 595 595
ESH: 5-23 kW
Lo Cooling (Y1)
356 354 359 359
Dehumid (D)
477 474 474 472
Hi Heating (W2)
529 529 529 526
Pin Setting 1100-0100
Lo Heating (W1)
434 425 425 420
Constant (G)
316 300 300 295
1
2
3
4
5
6
7
8
Model: HE-100
# Outlets
28
32
36
Cooling: 12.3 kW
Mode
Airflow in L/s
Heating: 21.1 kW
Hi Cooling (Y2)
418 422 434
ESH: 5-18 kW
Lo Cooling (Y1)
252 255 262
Dehumid (D)
330 330 335
Hi Heating (W2)
375 385 392
Pin Setting 1000-0100
Lo Heating (W1)
295 295 295
Constant (G)
245 208 219
1
2
3
4
5
6
7
8
Model: HE-100
# Outlets
32
36
40
Cooling: 14.1 kW
Mode
Airflow in L/s
Heating: 23.5 kW
Hi Cooling (Y2)
472 486 486
ESH: 5-20 kW
Lo Cooling (Y1)
283 293 293
Dehumid (D)
378 387 378
Hi Heating (W2)
427 439 432
Pin Setting 1010-0100
Lo Heating (W1)
340 347 335
Constant (G)
234 238 231
1
2
3
4
5
6
7
8
Model: HE-100
ON
ON
ON
BLACK INDICATES DIP SWITCH POSITION.
A heat loss/gain must be done prior to selecting a Hi-Velocity-HE
unit. Once a heat loss/gain is known based upon tonnage and vents required, select the appropriate HE unit and the
correct pin settings. If further adjustments are required for the L/s please refer to the extended
Pin Setting
section.
Module WIR
Hi-Velocity Wiring & Dip Settings (10/11)
Module WIR Hi-Velocity Wiring & Dip Settings (10/11)
ON
OFF
Minimum of
eight
2”
(51mm)
outlets per ton of cooling
(HE Duct = Minimum
four
outlets per ton)
Black
indicates dip switch position:
ESH
= Electrical Strip Heaters, minimum of 7
outlets per 5kW is required
EPC Circuit Board Pin Settings and Air Flow Data (Metric)