Instruction for use • Switch unit AGS 80 D
Seite 17 von 29
The following values are set at the factory:
Designation
Standard value
Upper alarm threshold source left
220 bar (250 bar sensor)
Lower alarm threshold source left
50 bar (250 bar sensor)
Upper alarm threshold source right
220 bar (250 bar sensor)
Lower alarm threshold source right
50 bar (250 bar sensor)
Upper threshold liquid gas vaporizer
18 bar (20 bar sensor)
Lower alarm threshold liquid gas vaporizer
9 bar (20 bar sensor)
Upper alarm threshold medium pressure
18 bar (20 bar sensor)
Lower alarm threshold medium pressure
9 bar (20 bar sensor)
Upper alarm threshold mains pressure
5,5 bar (12,5 bar sensor)
Lower alarm threshold mains pressure
4,5 bar (12,5 bar sensor)
Order of sources “Source II”
Cylinder rack left
Liquid gas vaporizer available
Yes
Pre-heater available
No
Number of short events within 1 hour
5
Switch pressure liquid gas vaporizer pressure Cold
→
R1
9 bar
Switch pressure medium pressure Cold
→
R1
9 bar
Switch pressure medium pressure R1
→
R2
9 bar
Switch delay Cold
→
R1
0.5 sec
Switch delay R1
→
R2
0.5 sec
Alarm delay cylinder rack left
2 sec
Alarm delay cylinder rack right
2 sec
Alarm delay liquid gas vaporizer
2 sec
Alarm delay medium pressure
2 sec
Alarm delay mains pressure
2 sec
Alarm delay liquid gas vaporizer – medium pressure
2 sec
Service interval
6 months
Service month
01 2009
Service phone number
02603-2004
Rest cache
50
Common contact – message with service
Yes
Common contact – message with overflowing cache
Yes
Common contact – message with too many temporary events
Yes
LCD contrast
32
Table 5: Factory settings