Description
of the menu navigation and adjustement values
6
21
Name
P26
min. Flue gas temperature (Code protection):
Setting the min. Flue gas temperature (80-150°C)
P27
Cleaning interval (Code protection)
Setting of the cleaning interval (1-90min.)
P28
Heatexchanger cleaning interval (Code protection)
Setting of the Heatexchanger cleaning interval (20-480min.)
P29
Heat exchanger cleaning time (Code protection)
Setting of the Heatexchanger cleaning time (10-100 sec.)
P30
Scorch time (Code protection)
Setting the scorch time (1-10min.)
P31
Burn-out time (Code protection)
Setting the Burn-out time (1-30min.)
P32
max. Combustion chamber temperature (Code protection)
Setting the Ignition combustion room (750-950°C)
P33
Switch on delay (Code protection)
Setting the Switch on delay (-15 to 10sec)
P34
Switch off delay (Code protection)
Setting the Switch off delay (-15 to 10sec)
P35
Suction time (Code protection)
Setting the Suction time (10-90sec.)
P36
Suction cycle
Setting up the number of suction cycles (10-99)
P37
Number of suction times
Setting up the number of suction times (1-6)
P38
Suction time 1 (Code protection)
Setting the time, when the boiler should suck pellets (00:00-23:59)
P39
Suction time 2 (Code protection)
Setting the time, when the boiler should suck pellets (00:00-23:59)
P40
Suction time 3 (Code protection)
Setting the time, when the boiler should suck pellets (00:00-23:59)
By pressing the button:
"On/Off":
The equipment is switched on/off
„F1“:
(
T) changes to the „TIME-MODE“-menu
„F2“:
scroll up
„F3“:
scroll down
„F4“:
Value can be changed
PS 20
6
-
P26
P27
P28
P29
P30
90
30
120
30
5
°C
min
min
Sec
min
T
20 %
F1
F2
F3
F4