Fault Reports and their correction
9
Betriebsanleitung_firematic_20-301_Touch_Englisch V1.2
57
9.1
Faults not indicated on the display (Maintenance)
Boiler output gradually
decreases
•
Ash/slag on the grate
•
Fly ash container full
•
Heat exchangers heavily clogged/
sooted up
•
Reduce cleaning intervals or
clean manually.
•
Empty the fly ash container.
•
Clean the heat exchangers.
Desired
operating
temperature
is
not
reached
•
Fuel of inferior quality.
•
Previous boiler output higher than
current boiler output
•
Fuel level too low
•
Replace fuel if necessary
•
Install a larger boiler
•
Increase fuel level
Ash is emitted from the
chimney
•
Fly ash container full
•
Fuel contains excessive fines or super
fines
•
Fan speeds too high
•
Chimney draught too high
•
Remove fly ash
•
Replace fuel if necessary or
retrofit flue gas deduster.
•
Reduce speeds
•
Retrofit chimney draught regulator