7.3
Fault table
Fault
Cause
Remedial action
Leak at the spindle
Gland nut loose
Retighten the gland nut
Gland packing defective
Replace the gland packing
Fit on the spindle damaged
Replace the spindle
Leak between bonnet
and body
Bonnet loose
Retighten the bonnet screws
Seal damaged
Replace seal
Ball valve does not
open / close
Gland nut overtightened
Loosen the gland nut
Tightness must still be ensured
7.4
Spare parts
We require the following details for your spare part orders:
Article no. of the spare part package,
desired delivery quantity,
dispatch and delivery address,
desired method of dispatch.
7.5
Returns / complaints
Use the Service form in case of returns/complaints.
Contact in case of service:
Herose.com › Service › Product service › Complaints
E-mail: [email protected]
Fax: +49 4531 509 – 9285
8
Disassembly and disposal
8.1
Notes regarding the disassembly
Take note of all national and local safety requirements.
The pipework system must be depressurised.
The medium and valve must be at ambient temperature.
Aerate / flush the pipework system in the case of corrosive and aggressive media.
8.2
Disposal
1. Dismount the valves.
Collect greases and lubricating fluids during dismantling.
2. Separate the valve materials:
Metal
Plastic
Electronic scrap
Greases and lubricating fluids
3. Carry out a sorted disposal of the materials.