7.3 

Fault table 

Fault 

Cause 

Remedial action 

  Safety valve does 

not respond 

Covers have not been 
removed 

  Remove covers 

Setting pressure too high 

  Replace the safety valve 

Back pressure not taken into 
account 

  Replace the safety valve 

  Not liftable 

Pressure below 85% of the 
set pressure 

  Lifting in the range ≥85 % of the set 

pressure without aids 

  Leak in the seat 

Foreign bodies between cone 
and seat, contaminated 
medium 

  Remove foreign bodies by briefly 

lifting / flush the system or replace 
the safety valve 

Seat damaged 

  Replace the safety valve 

Cone seal damaged 

  Replace the safety valve 

Safety valve has fluttered 

  See "Fluttering" 

  Damage to the 

inlet/outlet 

Transport damage 

  Replace the safety valve 

Wrong connecting thread / 
tightening torque too high 

  Replace the safety valve 

impermissible forces such as 
bending or torsional forces 
are being transmitted. 

  Install stress-free 

  Pressure surges 

Safety valve not mounted at 
the highest point 

  Install the safety valve at the 

highest point 

water not drained correctly or 
at all 

  Attach water drain according to 

regulations 

  Constantly 

blowing off 

Spring corroded by 
impermissible medium and 
broken 

  Replace the safety valve 

Cone seal damaged 

  Replace the safety valve 

  Fluttering 

Pressure loss in the supply 
line >3% 

  Reduce resistance through chamfer 

or radius in the connecting socket; 
choose a larger one if necessary 

Seals for inlet and outlet 
connector too small or not 
installed centrally 

  Change conditions 

Safety valves are too 
powerful 

  choose smaller safety valves 

Blow-off pipe too long or 
diameter too small 

  Use a larger nominal diameter or a 

back-pressure-compensating 
stainless steel bellows. The max. 
height is to be specified by the 
manufacturer. 

Inlet or outlet connector too 
small 

  Dimensions must be larger than the 

nominal inlet or outlet diameter 

Back pressure higher than 
10% or 15% respectively 

  Use back-pressure-compensating 

stainless steel bellows. The max. 
height is to be specified by the 
manufacturer. 

  Inadequate 

performance 

Safety valves dimensioned 
incorrectly for the plant 
conditions 

  Re-dimension and replace the 

safety valve 

Safety valves not being used 
in accordance with the 
applicable regulations 

  Change conditions 

Summary of Contents for 06810

Page 1: ...HEROSE GMBH ARMATUREM UND METALLE Operating instructions Angle safety valve Type 06810 06815 06820 06850 06855...

Page 2: ...oe Germany Phone 49 4531 509 0 Fax 49 4531 509 120 E mail info herose com Web www herose com 1st issue 08 2018 The transmission or duplication of this document and the reuse or communication of its co...

Page 3: ...ctions herose com 3 Table of contents 1 About these instructions 4 2 Safety 4 3 Transport and storage 7 4 Description of the safety valve 7 5 Assembly 10 6 Operation 11 7 Maintenance 12 8 Disassembly...

Page 4: ...operating instructions see section 4 5 Media Operating conditions and applications deviating from these require the approval of the manufacturer Only media may be employed to which the materials used...

Page 5: ...2 5 Additional equipment and spare parts Additional equipment and spare parts not conforming to the manufacturer s requirements can negatively affect the operational safety of the safety valve and cau...

Page 6: ...e support Additional loads such as traffic wind or earthquakes are not explicitly taken into account by default and require separate dimensioning Condensation in air conditioning cooling and refrigera...

Page 7: ...e of 20 C to 65 C 4 Description of the safety valve See catalogue page 4 1 Structure Design Directly acting angle safety valve spring loaded 4 2 Marking The safety valve is equipped with a marking for...

Page 8: ...ubject to Directive 2014 68 EU Pressure equipment directive of the European Parliament and of the Council article 2 section 4 4 4 Operating data Type d0 mm Pressure range bar Max back pressure Tempera...

Page 9: ...their intended purpose In this case a technical service life may be assumed in accordance with the underlying product standards e g EN1626 for shut off valves and EN ISO 4126 1 for safety valves The...

Page 10: ...d pitches Avoid damaging the connections The sealing surfaces must remain clean and intact Seal the safety valve using suitable seals No sealant sealing tape liquid sealing tape may enter the safety v...

Page 11: ...Liftability manual actuation for testing Liftable safety valves are equipped with an appropriate device above the spring cover Make liftable safety valves open at 85 of the set pressure without aids P...

Page 12: ...nspection and maintenance intervals in these operating instructions 7 2 1 Recommended inspection and maintenance intervals Inspection During commissio ning annuall y 2 years 5 years 10 years Correspon...

Page 13: ...est point water not drained correctly or at all Attach water drain according to regulations Constantly blowing off Spring corroded by impermissible medium and broken Replace the safety valve Cone seal...

Page 14: ...plaints E mail service herose com Fax 49 4531 509 9285 8 Disassembly and disposal 8 1 Notes regarding the disassembly Take note of all national and local safety requirements The pipeline system must b...

Reviews: