Operating instructions
herose.com
11
6
Operation
The maximum permissible pressure loss in the supply pipes to the safety valves may not exceed the
3% pressure difference between the response pressure and external back pressure on the safety
valve.
Vibrations are to be avoided.
6.1
Liftability (manual actuation for testing)
Liftable safety valves are equipped with an appropriate device above the spring cover.
Make liftable safety valves open at ≥85 % of the set pressure without aids.
Proceed as follows during the initial start-up, after breaks in operation and for checking the
function:
The valve is ready for operation.
1. Pull the lifting lever away from the spring cover until
blow-off of the operating medium is clearly audible.
2. Release the lifting lever again.