background image

Installation Manual                                                                                                

                                                                                                         

 

Wiring Instructions 

 

MPS100 Power Supply 

  The power supply (MPS100) requires an input of 115 volts AC, 50/60 Hz. Using 14-16 

gauge wires connect AC power to the BLACK (LINE), WHITE (NEUTRAL), and GREEN 
(GROUND) power supply wires.   

 

MC110A Control Unit 

  Matching wire color, connect the power supply RED +9VDC and BLACK -9VDC wires to 

the MC110A 

control module’s RED and BLACK 9-12 VDC input wires.      

  Matching wire color, connect the MC110A 

control module’s ORANGE and BLUE control 

wires to 

the MPM100 power module’s ORANGE and BLUE control wires.  See the 

Wiring 

Multiple MPM100 Power Modulators into a system 

section above for more information

 

 

 

 

MPM100 Power Modulator 

 

Connect the MPM100’s (BLACK) wire to the power panel Phase 1. 

  Co

nnect the MPM100’s (WHITE) wire to Phase 2 of the power panel with a dedicated wire. 

  Connect a wire from Phase 2 of the power panel to Line 2 of the heating devices.  

 

Connect the MPM100’s LOAD (RED) wire to the L1 line of the heating devices

.  

 

 

 

 

 

 

NOTE

: To ensure proper operation of your MicroZone system, a dedicated wire must be run 

from the load center Phase 2 to the WHITE wire of the MPM100 modulators. This will prevent 
lamp load current on Phase 2 from interfering with proper operation of the MPM100 modulator. 

(For 120V operation, Phase 1 is the 120V hot line and Phase 2 is the neutral line.)

 

 

Summary of Contents for MicroZone MC110A

Page 1: ...Installation Manual 10 31 2014 0 10V Automatic Lamp Mat Heating Control Installation Operation...

Page 2: ...on Overview 3 Mounting and Wiring 3 Conduit and Connections 3 Module Installation 4 Wiring Setup 4 Wiring Multiple MPM100 Power Modulators into a System 4 Wiring MPM100 Power Modulator 6 Wiring Instru...

Page 3: ...Place the controller away from motors and relays contactors that switch high current Do not install it in the same room where the animals live since the air tends to be corrosive to electronic circuit...

Page 4: ...e the animals live A separate room or hallway is a preferred location Do not install the modules where they will be subjected to harsh chemicals When fastening the covers to the units be sure to only...

Page 5: ...one system a dedicated Phase 2 wire must be run to the Modulators MPM100 s This will prevent load current on the Phase 2 wire from interfering with proper operation of the MPM100 modulator For 120V op...

Page 6: ...ch power modulator will have its own heating device circuit wiring Wiring MPM100 Power Modulator Ensure power is removed from the power distribution panel before wiring in the heating device feed circ...

Page 7: ...ring Multiple MPM100 Power Modulators into a system section above for more information MPM100 Power Modulator Connect the MPM100 s BLACK wire to the power panel Phase 1 Connect the MPM100 s WHITE wire...

Page 8: ...actory for repair Flashing AUTO indicator Communications between the Controller MC110A and the Modulator have failed The communications wiring may have been damaged or become disconnected Intermittent...

Page 9: ...f 12 MPM MicroZone Power Modulators within 500 feet using 18AWG two conductor wire MPM100 MicroZone Power Modulator Input Power 120 240VAC 16A Maximum Load Rating 0 120VAC or 0 240VAC 2kW 120V or 4kw...

Reviews: