
Installation and Operation Manual
HL-10P(LV) Installation Manual Ver 1.0
3
Part Number MAN-000024
Description
The House Link HL-10P Low Voltage (LV) provides a 2mV/V or 3mV/V output proportional to the weight of the selected
bin. The device will connect to the BinTrac Indicator BINS port in parallel with the Smart Summing Box. The BinTrac
Indicator transmits digital weight data which is converted to a proportionate millivolt output.
Installation
The HouseLink HL-10P(LV) is designed
to be used with the BinTrac Bin Weighing system. One HouseLink HL-10P(LV)
can be connected per displayed bin.
1. The HouseLink HL-10P(LV) should be mounted no more than 10
feet from the house control.
2. Using a two-conductor cable (ordered separately), connect the
green wire from the Smart Summing Box (or the BINS port on the
BinTrac Indicator) to the +COM (OUT) terminal in the HouseLink
HL-10P(LV) and the white wire from the Smart Summing Box (or
the BINS port on the BinTrac Indicator) to the -COM (OUT)
terminal in the HouseLink HL-10P(LV). See
Figure 1
.
3. Connect the HouseLink HL-10P(LV) to the house control by
connecting the +EXC (IN) to the + EXC terminal and the
–EXC (IN) to the –EXC terminal of the house control.
4. Finally, connect the +mV/V (OUT) from the HouseLink HL-10P(LV)
to the + SIG of the house control and the
–mV/V from the HouseLink
HL-10P(LV) to the
–SIG of the house control.
Setup & Configuration
Dip Switch Setup
The unit has four dip switches that need to be set up for configuration (circled in
Figure 2
).
Bin Selection (S1 and S2)
This setting allows you to control which bin the HL-10P(LV)
will send data from (see below). By default, S1 and S2 are
both in the OFF position (Bin A).
ZERO Tracking (S3)
This setting allows the ZERO to be tracked with the BinTrac
Indicator. Setting S3 to the ON position will allow the ZERO
to be tracked by the house controls. By default, dip switch S3
is in the OFF position.
Output Scale Selection (S4)
This setting provides a 3mV/V output at full scale. Setting S4 to the ON position will instead provide a 2mV/V at full scale.
By default, dip switch S4 is in the OFF position.
A
B
C
D
Figure 1
Figure 2
Figure 1