background image

 

 

   

 

EN

 – Translation of the original user manual -  2.0 | 2019 

43 

 

Fixed safety contact strips (SKL)  

6.5.2

 

The evaluation of the fixed safety contact strips (SKL) are always activated by the 
manufacturer.  The strips are connected as follows:  

 

Switch off the power supply to the motor drive. 

 

Connect the contact strip(s) for the OPEN direction to the terminal SKL 
open.  

 

Connect the contact strip(s) for the CLOSE direction to the terminal SKL 
close.  

 

Switch on the power supply to the control system.  

 

Check that the strips are correctly connected by checking the “Sensor 
display” screen and the response of the gate for the corresponding direction 
of movement in “Automatic mode”.  

 
 

 

Accompanying safety contact strips (ISK)  

6.5.3

 
The evaluation of the accompanying safety contact strips (SKL), connected via the 
ISK system, is also always activated by the manufacturer.  The ISK system (fixed 
SPK55 coil core only) is connected as follows:  

 

Switch off the power supply to the motor drive. 

 

Connect the ISK system (fixed coil core) to the ISK terminal.  

 

Switch on the power supply to the control system.  

 

Check that the accompanying strips are correctly connected by checking the 
“Sensor Display” screen and the response of the gate for the corresponding 
direction of movement in “Automatic mode”.  

 

If the evaluation of the ISK system is not activated in the control system, it is 
switched on by the following procedure:  

 

Menu:  “Service Access”, “Password Input”:  Enter password. 

 

Menu:  “Settings”, “Safety”, “Activate ISK”  

 

Exit menu  

 

 

Light barrier  

6.5.4

 
It is possible to connect one-way light barriers as well as reflex light barriers that 
work with an operating voltage of 24 V

DC

 directly to the control system.  The input 

signal of the light barrier is connected to terminal no. 2 with the designation 
“LB in”.  

Summary of Contents for HMD Basic

Page 1: ...2 0 2019 User Manual Gate with drive HMD Basic HMD24 Please read this original user manual before using this sliding gate for the first time Act in accordance with the manual and keep it in a safe pla...

Page 2: ...EN Translation of the original user manual 2 0 2019 2...

Page 3: ...IONS EMPLOYED 12 2 5 INTENDED USE 12 2 6 SAFETY DURING USE 12 2 7 SAFETY DURING INSTALLATION MAINTENANCE AND DISASSEMBLY 13 OPERATION 14 3 3 1 OPENING CLOSING SLIDING GATE NORMAL USE 14 3 2 OPEN CLOSE...

Page 4: ...s 39 6 4 1 Operating keys for hold to run operation 39 6 4 2 Stop function 40 6 4 3 Operating keys OPEN 40 6 4 4 Operating keys CLOSE 40 6 4 5 Setting up the partOPEN function pedestrian passage 41 6...

Page 5: ...w transmitters 59 7 11 2 Registering key functions 60 7 11 3 Deleting a transmitter 61 7 11 4 Deleting a transmission location 61 7 11 5 Deleting all transmitters 62 7 11 6 7 12 DIAGNOSTIC SUPPORT 62...

Page 6: ...o ensure that you can continue to operate your gate problem free in the long term Please read this user manual carefully before using the sliding gate Store the manual in a safe place to be able to re...

Page 7: ...37277 Heras UK Telephone 44 0 1302 364 551 Heras France Telephone 33 0 3 88 067 000 Heras Norway Telephone 47 22 900 555 Heras Sweden Telephone 46 0 77 1506050 1 3 DEFINITIONS USER OPERATOR ENGINEER U...

Page 8: ...mpatibility 305 2011 EC Construction Product Regulation The design and production has been executed compliant with the applicable product standard EN 13241 1 and the underlying standards EN 12604 EN 1...

Page 9: ...ate circuit If after measurement during commissioning it appears that the leakage current exceeds the permitted 3 5 mA an additional grounding in accordance with EN 60335 1 and IEC 30364 5 54 must be...

Page 10: ...tions below Note To prevent material damage you must observe the safety instructions below Information This is followed by further information or by a reference to other documents Warning Risk of limb...

Page 11: ...the safe operation of the gate All alterations or extensions to the gate must be carried out by qualified personnel using parts which the manufacturer has defined as suitable for such alterations or e...

Page 12: ...with the user The relevant options are laid down during hand over Carefully read this user manual before operating the gate You must always be familiar with the operating mode the gate is in 2 6 SAFET...

Page 13: ...can temporarily distort the gate When closing the gate the leaf is guided to its neutral position When opening the gate the leaf will move around somewhat This has no adverse consequences for the con...

Page 14: ...Illustration 2 Warning sticker bottom rail OPERATION 3 3 1 OPENING CLOSING SLIDING GATE NORMAL USE The gate can be operated using pulse operation for instance via a button or key switch The location...

Page 15: ...vertically off Pull the knob and turn it slightly to the left or right The motor falls down and the gate is manually operated Close the cabinet again Illustration 3 unlocking motor and gate 3 2 2 Lock...

Page 16: ...eters in a double version Applications include port areas company buildings office buildings storage sites garden and landscape areas high risk sites airports transport and distribution sites and park...

Page 17: ...ied engineer See the chapter 1 2 SERVICE MAINTENANCE 4 3 PHOTOCELLS Photocells detect whether there are obstacles in the path taken by the gate If an obstacle is detected the gate will stop immediatel...

Page 18: ...trol software is divided into separate function modules and is available to users in two possible operating modes hold to run mode automatic mode Hold to run control 4 5 1 The gate motor drive can be...

Page 19: ...omatic mode if the gate has not been installed fully yet If the gate has not been fully installed yet or if motor drive programming has not been completed yet the motor drive will work in a special sa...

Page 20: ...n of the original user manual 2 0 2019 20 Changing between operating modes is possible in the following directions Automatic mode Hold to run control mode Dead man s mode Automatic mode if safety has...

Page 21: ...nal user manual 2 0 2019 21 CONTROL UNIT AND DISPLAY READINGS 5 5 1 TOTAL VIEW OF HMD24 DRIVE UNIT Illustration 6 view of HMD24 drive unit cable strain relief cable bushing automatic fuse place for ex...

Page 22: ...ction and settings 3 2 line LC text display 4 Motor connection 5 Power supply connection 20 35 VDC 6 Fuse F2 for the control electronics 1 A black 7 Fuse F1 for the power electronics and the motor 10...

Page 23: ...a displayed table or within a memory area If the knob is pressed down a displayed value is accepted a different mode selected or a display or selection menu exited 5 4 LCD DISPLAY To show detailed inf...

Page 24: ...un operation Open Hold to run operation Gate opening is active Hold to run operation Close Hold to run operation Gate closing is active Heras HMD24 Automatic mode Automatic operating mode Rest status...

Page 25: ...re not displayed Display Meaning Sensors Start Rotating the selection switch to the left reaches the first entry in the sensor table Limit switch OPEN Value 2 x Current value of the limit switch for t...

Page 26: ...ction 8 2 of this document Examples of proactive display Immediately after the control system is switched on the message 250 ProgramInit is displayed for a short time to indicate that the control syst...

Page 27: ...y and provide for the specific behaviour for a defined gate Many of these parameters can be made accessible to users or gate control system fitters via the menu system Entering the password 5 4 6 The...

Page 28: ...automatically resets to the value 33333 If any number other than a correct password is set this number remains saved and is not reset to the value 33333 after 10 minutes It is possible to directly se...

Page 29: ...t recent events and faults including their time stamp operating time Temperature Display of the temperatures of the power electronics Motor current Display of the maximum motor currents that have occu...

Page 30: ...REFERENCES After the menu has been selected the main menu level appears This offers a choice of several submenus The menu system can be exited again using the first menu item END Reset takes the user...

Page 31: ...otor 8 Bootloader Peri 2 Service menu Menu back 1 Enter password Chap 5 4 6 2 Language Chap 5 7 Menu back 1 Dutch 2 English 3 German 4 French 5 Norwegian 6 Swedish 7 Danish 3 Mot Rotation Chap 7 1 4 T...

Page 32: ...ast Service 7 RESET Service Chap 7 8 5 2 Sensor Status Chap 7 12 3 3 System Logbook Chap 7 12 6 4 Temperatures Menu back 1 DC Temperature Chap 7 12 4 3 RESET Min Max 5 Motor current Menu back 1 MAX mo...

Page 33: ...2 Input In3 4 Menu back 1 Inp Variant 1 2 Inp Variant 2 3 Inp Variant 3 Chap 7 3 3 Safeties Menu back 1 Lightbarrier Chap 6 5 4 2 ISK activation Chap 6 5 1 3 JCM activation Chap 7 2 4 Referentie run...

Page 34: ...p 7 10 2 Save Chap 7 9 7 Status indicat Chap 7 6 Menu back 1 Gate status 1 2 Gate status 1 Outp 3 Gate status 2 4 Gate status 2 Outp 5 RF Remote Menu back 1 Active transm Chap 7 11 1 2 Prog transmi Ch...

Page 35: ...24 DC in terms of both mechanical assembly and electrical installation 6 1 ELECTRICAL CONNECTION For safety reasons the electrical installation must always be carried out by an authorised specialist W...

Page 36: ...are correctly connected to the input of the electronics Likewise great care should be taken to ensure that the grid power supply to the transformer and the protective ground are connected correctly C...

Page 37: ...VDC power supply able to supply a maximum current of 500 mA for the supply of the external devices command devices and sensors This supply voltage is fused on the printed circuit board by an automatic...

Page 38: ...osed contact For the functions open close and switchover impulse toggle pushbuttons with a normally open contact are connected as command devices For the functions OPEN In5 or partOPEN In4 it is also...

Page 39: ...ction is required for the limit switch connect this to 0 V Switch on power supply and check that the limit switch is connected correctly Operating keys for hold to run operation 6 4 2 Before a gate ca...

Page 40: ...in automatic mode with self locking an OPEN pushbutton normally open contact can be connected to the In5 input The input is configured such that when activated it moves the gate in the OPEN direction...

Page 41: ...in the menu as follows Menu Settings Set timer Runtime to partOPEN select lower or higher value increase or decrease opening width Exit menu Move gate from the CLOSED position to the partOPEN position...

Page 42: ...the control system software Indus system with accompanying safety contact strips 6 5 1 The evaluation of the ISK inductive cable transmission system from manufacturer ASO GmbH for the gate accompanyin...

Page 43: ...d via the ISK system is also always activated by the manufacturer The ISK system fixed SPK55 coil core only is connected as follows Switch off the power supply to the motor drive Connect the ISK syste...

Page 44: ...ase Illustration 9 Connection of tested one way light barrier Illustration 10 Connection of reflex light barrier The two representations show as examples the different connections of a one way light b...

Page 45: ...tomatic mode In the HMD24 this is the default value in the menu Overview installation plan of the inputs 6 5 6 The HMD24 is configured for operation with limit switches The following drawing shows a t...

Page 46: ...wn in the figure below Illustration 12 Connection of relay to 24 VDC Attention When connecting external loads to the 24 V power supply from the control system the maximum current carrying capacity of...

Page 47: ...ht hand terminal no 2 towards the housing side The shielding of the aerial cable is connected to the left hand terminal no 1 towards the centre of the board Illustration 13 Electrical connection of ra...

Page 48: ...ate is now moving in the correct direction 7 2 CONNECTION OF A JCM RADIO SYSTEM Integrating other sensors into the safety circuit for the fixed contact strips makes it possible for the control system...

Page 49: ...associated transmitter of the JCM RB3T868 radio transmission system as shown in the following figure Illustration 15 Example connection of safety contact strips to the JCM RB3R686 transmitter The thre...

Page 50: ...re listed in the following three tables Variant 1 Terminal no Designatio n Input function 3 In8 Hold to run OPEN pushbutton e g key switch on the gate 4 In7 Hold to run CLOSE pushbutton e g key switch...

Page 51: ...ts maximum speed just before reaching the limit switches the control system must measure the motor runtime between the gate s limit positions by performing a reference movement It can then use this ru...

Page 52: ...S The output of relay Rel1 has been set up for the flashing function by the manufacturer A self flashing light for 24 V is connected to relay Rel1 as follows Switch on the power supply to the control...

Page 53: ...0 seconds If a value of 0 is entered the closing run timer is switched off and the gate remains open until the next CLOSE command Menu Settings Set timer TMR hold open set to xxx Example If the TMR ho...

Page 54: ...value can also be entered by the customer without entering a password The conditions for reversing upon the activation of a safety strip are the same for this closing run timer as those already descri...

Page 55: ...PEN direction the moment at which the gate is braked before reaching the OPEN limit switch is too late this preset time value can be increased In the factory setting the default time is 600 The value...

Page 56: ...stem The value zz is the maximum number of gate cycles in 1000 cycles CLOSE OPEN CLOSE until the service request The adjustable values mean 0 no maintenance request after number of movement cycles 25...

Page 57: ...activation of the flashlight for the maintenance request can be parametrised as follows Menu Service Access Password Input Enter password Menu Settings Special parameters Maintenance action set 0 to...

Page 58: ...follows Menu Service Access Password Input Enter password Menu Settings Param Backup activate Backup 7 10 RELOADING PARAMETERS The parameters stored as a backup copy in a separate memory area can be...

Page 59: ...ring new transmitters 7 11 2 The following pre defined gate functions can be executed with HERAS handheld radio transmitters using three keys 1 Key top left Gate OPEN function 2 Key top right Gate CLO...

Page 60: ...dedicated memory location is used for each key to be registered The registering of the individual key functions of a transmitter can be carried out using the following menu items Menu item Function 3...

Page 61: ...required key on the handheld transmitter to delete the transmitter from the control system memory After deletion the display jumps back to the menu If the program does not recognize any valid and sto...

Page 62: ...which can be used to put the control system into operation and rectify any errors that have occurred Version display 7 12 1 The version of the control system can be displayed as follows Menu Identific...

Page 63: ...us of the output relay is shown with its logical values An activated relay is marked with 1 The sequence corresponds to the outputs Rel3 to Rel1 In this example relay Rel3 is active Movement cycles 52...

Page 64: ...e minimum and maximum value of the displays in question to the current temperature Motor current display 7 12 5 The maximum current from the last motor movement and the maximum motor current in the po...

Page 65: ...possible to scroll through the entries in this log memory in chronological order The very first entry in this log always contains information about the program initialisation 250 ProgramInit The speci...

Page 66: ...xed StripCLOS E Fixed safety contact strip CLOSE was activated a 0 is stored immediately after the text if the motor was not active 27 Acc StripOPEN Accompanying safety contact strip OPEN was activate...

Page 67: ...a halt 197 START Restart of the program 201 ROM error The motor controller has detected a program memory error fatal exception error 202 EEPROM Bcc An error occurred when accessing the EEPROM may occu...

Page 68: ...positions undef The limit positions of the gate are undefined for the control system software e g both limit switch contacts open 217 EEPR err Txt The sought after display text was not found in the m...

Page 69: ...o an active movement command Check inputs 239 LightbarrierTst errThe light barrier test has shown up an error 240 EMERGENCYtst err The self test failed at the emergency input 241 SPI BCC err A checksu...

Page 70: ...ff and protected from unauthorized switching on If the gate must be moved manually first turn the system circuit breaker in themotor cabinet to the off position and protect it from being switched on e...

Page 71: ...chor and bolted connections Check wear of running wheels upper guide wheels and the surface on which they run Check welded joints damage to coating and zinc Check for damage and the operation of safet...

Page 72: ...ts back and then dispose of them in an appropriate manner The Delta gate has highly tensioned cables fitted in the bottom rail If these cables are cut they can snap with great force This can lead to s...

Page 73: ...d on power network max 10 A External power supply for external 24 V devices 24 VDC stabilised 5 max 500 mA protected with self resetting semiconductor fuse Control inputs 24 VDC typical 4 mA 12 V inac...

Page 74: ...lues Dimensions H x W x D 160 x 270 x 110 mm Weight 3 5 kg with ring core transformer Protection class IP54 Temperature range 20 C to 55 C Humidity range max 99 non condensing The functions described...

Page 75: ...EN Translation of the original user manual 2 0 2019 75 Appendix A Declarations Dop DoC...

Page 76: ...EN Translation of the original user manual 2 0 2019 76...

Page 77: ...EN Translation of the original user manual 2 0 2019 77 Appendix B ELECTRIC DIAGRAM HMD24...

Page 78: ...EN Translation of the original user manual 2 0 2019 78...

Page 79: ...EN Translation of the original user manual 2 0 2019 79...

Page 80: ...EN Translation of the original user manual 2 0 2019 80...

Page 81: ...EN Translation of the original user manual 2 0 2019 81...

Page 82: ...EN Translation of the original user manual 2 0 2019 82...

Page 83: ...EN Translation of the original user manual 2 0 2019 83...

Page 84: ...EN Translation of the original user manual 2 0 2019 84...

Page 85: ...EN Translation of the original user manual 2 0 2019 85...

Page 86: ...EN Translation of the original user manual 2 0 2019 86...

Page 87: ...EN Translation of the original user manual 2 0 2019 87...

Page 88: ...Local supplier stamp Lokal terf rs ljare st mpel...

Reviews:

Related manuals for HMD Basic